11
W415-0381 / H / 12.07.07
V
1
HORIZONTAL TERMINATION
See graph to determine the re-
quired vertical rise V
T
for the
required horizontal run H
T
.
For vent confi gurations requiring more than one 45º and 90°
elbow the following formulas apply:
Formula 1: H
T
< 4.2 V
T
Formula 2: H
T
+ V
T
< 24.75 feet
FIGURE 8
REQUIRED
VERTICAL
RISE IN
INCHES (V
T
)
HORIZONTAL VENT RUN PLUS OFFSETS IN FEET
when
(H
T
)
>
(V
T
)
Simple venting confi guration (only one 45º and 90° elbow)
Example 2:
V
1
= 4 ft
V
2
= 1.5 ft
V
T
=
V
1
+
V
2
= 4 ft + 1.5 ft = 5.5 ft
H
1
=
2
ft
H
2
=
1
ft
H
3
=
1
ft
H
4
=
1.5
ft
H
R
=
H
1
+
H
2
+
H
3
+
H
4
= 2 + 1 + 1 + 1. 5 = 5.5 ft
H
O
= .03(one 45º elbow + four 90º elbows -135º)
=.03(405-135)=8.1ft
H
T
=
H
R
+
H
O
= 5.5 + 8.1 = 13.6ft
H
T
+ V
T
= 13.6 + 5.5 = 19.1ft
Formula 1:
H
T
< 4.2 V
T
4.2
V
T
= 4.2 x 5.5 = 23.1 ft
13.6 < 23.1
Formula 2:
H
T
+ V
T
< 24.75 feet
19.1
<
24.75
Since both formulas are met, this vent confi guration is
acceptable.
H
4
90°
H
3
H
1
90°
H
2
90°
FIGURE 9
45°
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
V
2
90°
Содержание BGD42