background image

15

W415-0381 / H / 12.07.07

  

DO  NOT  CLAMP     

THE FLEXIBLE

LINER

FIGURE 24b

1.

 Fasten the roof support 

to the roof using the screws 
provided. The roof support 
is optional. In this case the 
venting is to be adequately 
supported using either an al-
ternate method suitable to the 
authority having jurisdiction or 
the optional roof support. 

2. 

Stretch the inner 

vent pipe 

to the required length. Slip 

the 

vent pipe

 a minimum of 2” over the inner 

sleeve of the air terminal connector and secure 
with 3 #8 screws. Seal using a heavy bead of 
the high temperature sealant W573-0007 (not 
supplied). 

3.

 Repeat using the outer fl ex 

vent pipe

4.

 Thread the air terminal connector / liner as-

sembly down through the roof. The air terminal 
must be located vertically and plumb.  Attach 
the air terminal connector to the roof support, 
ensuring that the top of the air terminal is 16” 
above the highest point that it penetrates the 
roof. 

FIGURE 20

1.

 Stretch the 5" diameter fl exible 

vent pipe

 to the required length 

taking into account the additional length needed for the fi nished wall 
surface. Slip the liner a minimum of 2" over the inner sleeve of the 
air terminal and secure with 3 #8 screws. Apply a heavy bead of the 
high temperature sealant (W573-0007 not supplied).

2.

 Using the 8" diameter fl exible 

vent pipe

, slide over the outer 

combustion air sleeve of the air terminal and secure with 3 #8 screws. 
Seal as before.

The air terminal mounting plate may be recessed into the exterior 
wall or siding by 1½", the depth of the return fl ange.

4. 

Apply a heavy bead of the high temperature sealant W573-0007 

(not supplied), Mill Pac, to the inside of the 5" 

vent pipe 

approximately 

1" from the end. Slip the 

vent pipe

 a minimum of 2" over the fi replace 

vent collar and secure with 3  #8 screws. 

5. 

Using the 8" diameter fl exible 

vent pipe

, apply sealant W573-

0002 (not supplied), slide a minimum of 2" over the fi replace combus-
tion air collar and secure with 3 #8 screws.

6. 

If more liner needs to be used to reach the fi replace, couple 

them together as illustrated. The vent system must be supported 
approximately every 3 feet for both vertical and horizontal runs. Use 
noncombustible strapping to maintain the minimum 1" clearance to 
combustibles.

7.

 The vent heat shield 

must be installed only when 
terminating horizontally. Re-
move the two screws nearest 
the vent collars on the top of 
the fi replace. Align the vent 
heat shield (supplied) and 
secure. Adjust the vent heat 
shield to touch the firestop 
spacer.

FIGURE 21

HORIZONTAL AIR TERMINAL INSTALLATION

VERTICAL AIR TERMINAL INSTALLATION

FIGURE 22

Use only approved flexible 

vent pipe

 kits marked:

"Wolf  Steel Approved Venting" as iden-
tified by the stamp only on the 7” outer 

vent pipe

.

USING FLEXIBLE VENT COMPONENTS

For safe and proper operation of the fireplace, follow the venting 
instructions exactly.

All inner exhaust and outer intake vent pipe joints may be sealed 
using either Red RTV high temp silicone sealant or Black high 
temp Mill Pac with the exception of  the fireplace exhaust flue 
collar which must be sealed using Mill Pac (not supplied).

3.

 Insert the 

vent pipe assemblies

 through the fi restop maintaining 

the required clearance to combustibles. Holding the air terminal (let-
tering in an upright, readable position), secure to the exterior wall and 
make weather tight by sealing with caulking (not supplied).

FIGURE 23

Do not allow the inside 

vent pipe 

to 

bunch up on horizontal or vertical 
runs and elbows. Keep it pulled tight. 
A 1 1/4" air gap between the liner and 
outer liner all around is required for 
safe operation. A spacer is required 
at the start, middle and end of each 
elbow to ensure this gap is maintained. 

See Figure 20.

Spacers are attached to the inner fl ex 
liner at predetermined intervals to 
maintain a 1 1/4" air gap to the outer 
fl ex pipe. These spacers must not be 
removed.

FIGURE 24a

NOTE:

 Eight (8") inches is the minimum bend radius allowed for the 

8" diameter 

fl exible vent pipe

.

!

WARNING

ELBOWS

SPACERS

Содержание BGD42

Страница 1: ...1 W415 0381 H 12 07 07 W415 0381 H 12 07 07 10 00...

Страница 2: ...nts toddlers from touching hot surfaces Even after the fireplace is out the glass and or screen will remain hot for an extended period of time Check with your local hearth specialty dealer for safety...

Страница 3: ...venting components used in the installation of the replace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life subject to the following conditions During...

Страница 4: ...rity having jurisdiction the certi ed high altitude input rating shall be reduced at the rate of 4 for each additional 1 000ft Maximum output for natural gas is 19 500 BTU hr at an ef ciency of 68 5 w...

Страница 5: ...5 W415 0381 H 12 07 07 FIGURE 1 INSTALLATION OVERVIEW FIGURE 2...

Страница 6: ...Direct Temp and American Metal Amerivent follow the installation procedure provided with the venting components All outer pipe joints of these venting systems must be sealed using Red RTV Hight Temper...

Страница 7: ...AIR TERMINAL LOCATION CLEARANCES 32 32 32 32 32 32 4 Using a soffit heat shield W585 0096 or equivalent the distance may be reduced to a minimum of 18 It is recommended to maximize the distance to th...

Страница 8: ...at when nal grading is completed the bottom air slot is located a minimum of 12 above grade FIGURES 4 a b FIGURE 5 TYPICAL VENT INSTALLATIONS NOTE When terminating vertically the restrictor plate W500...

Страница 9: ...tal run horizontal run verti cal rise to maximum of 40 feet vertical rise is less than horizontal run horizontal run verti cal rise to maximum of 24 75 feet 4 2timesthe vertical rise equal to or great...

Страница 10: ...of offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the rst 45 and 90 offset has a zero value and is shown in the f...

Страница 11: ...T when HT VT Simple venting con guration only one 45 and 90 elbow Example 2 V1 4 ft V2 1 5 ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Страница 12: ...et 25 9 40 Since both formulas are met this vent con guration is acceptable when HT VT Simple venting con gurations FIGURE 10 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET...

Страница 13: ...40 Since both formulas are met this vent con guration is acceptable REQUIRED VERTICAL R I S E I N FEET VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT FIGURE 12 The shaded area within the lines represe...

Страница 14: ...learance of 2 all around the vent pipe on all horizontal runs to combustibles is required Use restop spacer W010 1778 supplied VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all ver...

Страница 15: ...combus tion air collar and secure with 3 8 screws 6 If more liner needs to be used to reach the replace couple them together as illustrated The vent system must be supported approximately every 3 feet...

Страница 16: ...erminal sleeves engage into the vent pipes and sealant Secure the terminal to the exterior wall and make weather tight by sealing with caulking not supplied Theairterminalmountingplatemaybe recessed i...

Страница 17: ...h a 5 collapsed telescopic pipe to the last section of rigid piping Secure with screws and seal Repeat using a 8 telescopic pipe 10 Run a bead of high temperature sealant W573 0007 not sup plied Mill...

Страница 18: ...is positioned and the vent system is installed Use 2x4 s and frame to local building codes FIGURES 33 It is not necessary to install a hearth extension with this replace system When roughing in the r...

Страница 19: ...Centre the nailing tab vertically on the corner post Figure 36 a Drill through the centre of the top and bottom slots in the nailing tab Secure using the two sheet metal screws supplied This allows t...

Страница 20: ...clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of the clips forward while push ing the louvre assembly back Lift the clip B HING...

Страница 21: ...g embers for a maximum glowing effect Log colours may vary During the initial use of the replace the colours will become more uniform as colour pigments burn in during the heat activated curing proces...

Страница 22: ...ll automatically start approxi mately 10 minutes after lighting the fireplace and will run for ap proximately 30 45 minutes after the fireplace has been turned off Use of the fan increases the output...

Страница 23: ...valve has an interlock device which will not al low the pilot burner to be lit until the thermocouple has cooled Allow approximately 60 seconds for the thermocouple to cool When lighting and re lighti...

Страница 24: ...e gasket Adjust the pilot screw to provide properly sized ame Turn in a clockwise direction to reduce the gas ow Air shutters have been factory set open according to the chart below These settings are...

Страница 25: ...LANT 39 W175 0166 5 COUPLER 39 W175 0002 8 COUPLER 40 L42K LOUVRE KIT UPPER LOWER BLACK 40 L42PB LOUVRE KIT UPPER LOWER POLISHED BRASS 40 L42SS LOUVRE KIT UPPER LOWER BRUSHED STAINLESS STEEL 41 GDOI42...

Страница 26: ...26 W415 0381 H 12 07 07...

Страница 27: ...le and valve connection replace thermocouple replace valve Faulty valve replace Pilot burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defec tive co...

Страница 28: ...door gasketing is not broken or missing and that the seal is tight check that both 5 and 8 vent liners are free of holes and well sealed at all joints check that minimum rise per foot has been adhered...

Отзывы: