EN
W415-2354 / B / 12.09.20
29
rough framing
MINIMUM REAR VENT CLEARANCES
For rear vent termination not exceeding 10" (254mm) of horizontal vent run.
* See "venting" section.
REAR EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 44" (111.8cm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
24 1/8"
[61.2cm]
MINIMUM
PLUS RISE*
COMBUSTIBLE
NON-COMBUSTIBLE
1"
[25mm]
3"
[76.2mm]
BRICK
0” (0mm) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
9 3/8"
[238mm]
24"
[61cm]
MINIMUM
PLUS RISE*
COMBUSTIBLE
NON-COMBUSTIBLE
1"
[25mm]
3"
[76.2mm]
BRICK
0” (0MM) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
6 3/8"
[162mm]
41"
[104.1cm]
10"-20"
[254mm-50.8cm]
VENT RUN
11 1/2"
[292mm]
44
"
[111.8cm]
1"-10"
[25mm-254mm]
VENT RUN
54
"
[137.2cm]
CEILING
(MIN)
INCOMBUSTIBLE
BRIQUE
0” (0MM) SI LES MATÉRIAUX
SONT INCOMBUSTIBLES,
COMME DE LA BRIQUE
ET DE LA PIERRE.
INCOMBUSTIBLE
BRIQUE
0” (0MM) SI LES MATÉRIAUX
SONT INCOMBUSTIBLES,
COMME DE LA BRIQUE
ET DE LA PIERRE.
24"
[61cm]
MINIMUM
PLUS LA PENTE*
COMBUSTIBLE
1"
[25mm]
3"
[76,2mm]
6 3/8"
[162mm]
41"
[104,1cm]
10"-20"
[254mm-50,8cm]
ÉVENTS
11 1/2"
[292mm]
24 1/8"
[61,2cm]
MINIMUM
PLUS LA PENTE*
COMBUSTIBLE
1"
[25mm]
3"
[76,2mm]
9 3/8"
[238mm]
44
"
[111,8cm]
1"-10"
[25mm-254mm]
ÉVENTS
54
"
[137,2cm]
PLAFOND
(MIN)
Ceiling
Enclosure
Plafond
Enceinte
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible
wall penetration.
24"
(61cm)