Page 1 of 54   

CLIENT # LC773211 

 

          THE AUSTIN 65L 
               38,000 BTU 

   

Natural Gas & Propane 

Installation and Operating Instructions 

 
 

MODEL:

 

AUSTIN-65G-NG-DELUXE, AUSTIN-65G-LP-

DELUXE 

 

 

 
 

 
 

                

 

 
 

 

 
 
 

WARNING 

IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR 

EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH. 

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or 

any other appliance. 

WHAT TO DO IF YOU SMELL GAS: 

 

Do not try to light any appliance 

 

Do not touch any electrical switch; do not use any phone in your building 

 

Immediately call your gas supplier from a neighbour’s phone. Follow gas supplier’s 
instructions 

 

If you cannot reach your gas supplier, call the fire department. 

Installation and service must be performed by a qualified installer, service agency or gas 
supplier. 

WARNING: Improper installation, adjustment, alteration, services or maintenance can cause 
injury or property damage. Refer to this manual. For assistance or additional information 
consult a qualified installer, service agency or the gas supplier. 

INSTALLER: Leave this manual with the appliance. 
 
CONSUMER: Retain this manual for future reference.

 

PLEASE READ THIS MANUAL BEFORE 

INSTALLING OR USING THIS APPLIANCE.  

SAVE THIS MANUAL FOR FUTURE 

REFERENCE. 

A BARRIER DESIGNED TO REDUCE THE RISK OF 
BURNS FROM THE HOT VIEWING GLASS IS 
PROVIDED WITH THIS APPLIANCE AND SHALL BE 
INSTALLED.

 

Summary of Contents for AUSTIN-65G-LP-DELUXE

Page 1: ...plier from a neighbour s phone Follow gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or gas supplier WARNING Improper installation adjustment alteration services or maintenance can cause injury or property damage Refer to this manual For assistance or additional informatio...

Page 2: ...s un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incendies L installation et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz AVERTISSEMENT Une mauvaise installation de réglage la modification de services ou de maintenance peut causer des dommages corporels...

Page 3: ...ass Media Installation 32 3 3 5 Door Installation 33 34 3 3 6 Safety Screen 34 3 3 7 Initial Firing 35 3 3 8 Pilot Flame Adjustment 35 3 3 9 Primary Air Adjustment 35 36 3 3 10 Altitude Adjustment 36 3 3 11 Fan Access 36 38 3 3 12 Gas Valve Access 38 4 0 MAINTENANCE 4 1 Maintenance Safety 39 4 2 Recommended Service 39 4 3 Glass Cleaning 40 4 4 Burner Pilot Cleaning 40 4 5 Valve Pilot Replacement 4...

Page 4: ...iques et intoxication au monoxyde de carbone DUE TO HIGH TEMPERATURES THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION YOUNG CHILDREN SHOULD BE SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE CLOTHING OR OTHER FLAMM...

Page 5: ...reil doit être remplacé avant de faire fonctionner l appareil Installation et réparation doit être effectuée par un technicien qualifié L appareil doit être inspecté avant son utilisation et au moins annuellement par un technicien qualifié Un nettoyage plus fréquent peut être nécessaire en raison de peluches provenant des tapis literie etc Il est impératif que les compartiments de contrôle les brû...

Page 6: ...ORIFICE SIZE 0 4500 FORMAT D ORIFICE 2 X 45 DMS 2 X 56 DMS AIR SHUTTER VOLET DE L AIR OPEN 1 8 min 3 175mm FULLY OPEN CONTROL VALVE TYPE TYPE DE SOUPAPE Skytech AF 40004 Skytech AF 40004 VENTING ÉVACUATION 2 ply aluminum vent Selkirk Duravent Security Venting ICC Venting or Metal Fab Venting 2 ply aluminum vent Selkirk Duravent Security Venting ICC Venting or Metal Fab Venting FAN VENTILATEUR Vari...

Page 7: ...to comply will void the warranty This appliance has been certified for use with natural gas and propane This appliance is not for use with solid fuels CODES D INSTALLATION Cet appareil est un appareil à évent direct qui attire tous l air de combustion provenant de l extérieur du bâtiment par une entrée d évent L installation doit se conformer aux codes locaux En l absence de codes locaux l install...

Page 8: ...es will activate the setup mode Setup mode can also be activated by pressing the FLAME REAR and PROG TIME buttons simultaneously for 5 seconds The control will exit setup mode if no button is pressed for 20 seconds Appropriate icon on LCD will flash when ready for setup Press the UP or Down button in setup mode to change the temperature scale Press SET button to skip or advance to Fuel Type setup ...

Page 9: ...ntrol to operate the unit for up to 3 hours in 10 minute increments It can be operated in either the Manual or Thermostat Modes To enter Timer Mode press and release the TIMER button The Timer icon will flash Press the UP or DOWN button to set the running time in 10 minute increments Press and release the SET button The timer will run for the set time duration Pressing the TIMER button while in Ti...

Page 10: ...e the control out of Child Lock out mode repeat the above step CP will disapper from the screen Learn Function To program the system to a transmitter press the LEARN button on the Main Module A single audible beep will be heard Press the MODE button on the transmitter to learn the transmitter to the system A series of beeps will be heard Up to two additional NON THERMOSTATIC transmitters can be us...

Page 11: ...t rester clair et exempt de matériaux combustibles essence et autres vapeurs et liquides inflammables The flow of combustion and ventilation air shall not be obstructed Le débit de combustion et de ventilation ne doit pas être obstrué The combustion air supply shall be in the same pressure zone as the drafthood relief opening on an appliance equipped with a drafthood or as the vent outlet on an ap...

Page 12: ...ers young children and at risk individuals out of the room and away from hot surfaces Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent cleaning may be req...

Page 13: ...ttempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to the lowest setting 3 T...

Page 14: ...quer une explosion ou un incendie D N utilisez pas cet appareil s il a été plunge dans l eau meme partiellement Faites inspecter l appareil par un technician qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l eau INSTRUCTIONS D ALLUMAGE 1 ARRÊTEZ Lisez les instructions de sécurité sur la portion supérieure de cette etiquette 2 Réglez le thermosta...

Page 15: ...t s components as this will damage the valve Ne pas communiquer 120 VAC à la valve de contrôle du gaz ou de ses composantes car cela endommagerait la vanne 3 2 UNPACKING Please check the appliance carefully for any damaged or missing components specifically check the glass condition Report any problems to your dealer within 30 days of purchase 3 3 INSTALLATION For satisfactory results it is necess...

Page 16: ...GRAM PAGE 18 MINIMUM CLEARANCES TO COMBUSTIBLES A 58 TO INTERNAL CEILING B 3 5 TO INTERNAL BACK COMBUSTIBLES C 17 5 TO BACK WALL FROM FRONT OF UNIT D 6 FROM EDGE OF FIREPLACE TO SIDE WALL E 39 FROM BOTTOM OF FIREPLACE TO STEEL STUD F 2 TO INTERNAL SIDE COMBUSTIBLES G 45 MINIMUM FROM BOTTOM OF FIREPLACE TO MANTLE SEE DIAGRAM NEXT PAGE 0 BASE OF UNIT TO FLOOR A B C D E F G 58 00 ...

Page 17: ...ences du fournisseur de gaz Le tableau placement manteau sur cette page illustre les dimensions et les emplacements admissibles cheminée L angle de 45 degrés peut être utilisé pour déterminer la taille permise manteau repose sur l élévation au dessus de la garniture unités supérieures CAU TION ATTENTION When using paint or lacquer to finish the mantel such paint or lacquer must be heat resistant u...

Page 18: ...MBUSTIBLE MATERIAL MATIERE NON COMBUSTIBLES Non combustible material will be supplied by the manufacturer This must be installed on top of the fireplace as shown above to meet installation codes Matériaux non combustibles seront fournis par le fabricant Ce doit être installé sur le dessus du foyer comme indiqué ci dessus pour répondre aux codes d installation 40 00 TO TOP OF NON COMBUSTIBLE BOARD ...

Page 19: ...em at test pressures equal to or less than 1 2 psi 3 45 kPa Cet appareil doit être isolé de l alimentation en gaz en fermant son robinet arrêt pendant tout test de pression de la canalisation de gaz à une pression égale ou inférieure à 1 2 psi 3 45 kPa The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at...

Page 20: ...tateur 1604247B ICC évacuation avec adaptateur ou Metal Fab évacuation directe à l utilisation de Metal Fab adaptateur partie 4DDA Installez les composants de ventilation selon les instructions du fabricant en veillant à utiliser des entretoises voir figure 5 tous les 5 pour assurer un espacement correct est maintenu entre l apport d air et l échappement Pente tuyau horizontal d au moins 1 4 6 mm ...

Page 21: ...ation cap 4DT HC The maximum vertical system consists of Dura Vent adapter Part 0924N3 directly on top of unit or Selkirk adapter Part 1604247B Up to 34 10363 mm of vertical length Fire stop Flashing Collar Dura Vent Termination cap part 0991 or Selkirk Termination cap part 4DT VC ICC VENTING The minimum vent system for horizontal termination must consist of ICC adapter directly on top of unit 15 ...

Page 22: ...rmination cap part SV4CGV Use a ceiling fire stop when penetrating a ceiling or floor Use a wall thimble when penetrating an inside or outside wall Vent terminals shall not be recessed into a wall or siding Metal Fab Venting The minimum vent system for horizontal termination must consist of Metal Fab adapter Part 4DDA directly on top of unit 15 305mm vertical length of vent 90 degree elbow 15 305 ...

Page 23: ...izontal termination cap part IMC1070A or IMC1070B Note 2 Ply Horizontal venting shall be supported by means of a steel strap every 3 The maximum vertical system consists of Up to 34 10363mm of vertical length Fire stop Flashing Collar Adapter from flex to Simpson Dura Vent part P574 Termination cap part 0991 A maximum of 4 90 degree bends can be used on the vertical installation venting The maximu...

Page 24: ... values are in feet EXAMPLES MINUMUM VERTICAL V1 MAXIMUM HORIZONTAL H1 H2 H3 H4 4 10 8 20 NOTE All vent dimensions are measured from the appliance surface where the vent connects to the point where exhaust gases exit the termination REMARQUE Toutes les dimensions sont mesurées à partir d aération de la surface de l appareil où l évent se connecte au point où les gaz d échappement de sortie de la r...

Page 25: ...Page 25 of 54 34 20 A A B B Example Where A A Vertical 2 And B B Horizontal 5 15 MINIMUM 15 MAXIMUM ...

Page 26: ...to follow above instructions for resealing venting when reconnecting to system FIGURE 7 VENT RESTRICTOR INSTALLATION VENT RESTRICTOR To fasten the Restrictor Plate to the ceiling of the firebox 1 Remove the 2 screws that are in place 2 Align holes in the Restrictor that match the required degree of restriction 3 Fasten Restrictor Plate back in place NOTE A minimum clearance to combustibles must be...

Page 27: ... pipe Mark the center line of the pipe facing the wall allowing for a 1 4 rise per foot of horizontal example 10 ft of horizontal would require a rise of 2 5 NOTE ALLOWING THE VENT PIPE TO SLOPE DOWN TOWARDS THE VENT TERMINATION COULD CAUSE POOR COMBUSTION AND OR HIGH TEMPERATURES THAT MAY PRESENT A FIRE HAZARD PERMETTRE LA tuyau de ventilation vers descendent vers la sortie de ventilation POURRAI...

Page 28: ...x head sheet metal screws then attach the 7 vent to the termination and fasten with 4 8 x hex head sheet metal screws be sure that the flex vent overlaps the termination collars a minimum of 2 Then attach the termination to the exterior wall using four wood screws through the holes in the corner of the vent terminal The next step is to apply a bead of mil pac or RTV 106 to top of the 4 exhaust col...

Page 29: ... and frame as shown in the diagram below NOTE ALWAYS CHECK YOUR LOCAL CODES BEFORE INSTALLING VENTING CLEARANCES ETC MAY VARY FROM STATE TO STATE PROVINCE TO PROVINCE TOUJOURS vérifier les codes locaux avant l installation VENTILATION ETC DÉGAGEMENTS peut varier d ÉTAT PROVINCE NOTE CONSULT DURAVENT PARTS LIST OR SIERRA FLAME S FIREPLACE MANUFACTURING PARTS LIST FOR PART NUMBERS FOYER Duravent CON...

Page 30: ... 2 from any wall To prevent water seepage install the flashing with upper portion under the roofing material and the lower portion over the roofing material Note Do not fasten down until the final adjustments to the vent have been made The diagram at right shows the minimum clearances as per the chart on page 31 3 12 from grade ...

Page 31: ... M Clearance under veranda 12 in 30 cm porch deck or balcony 0 0 3 3 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings Permitted only if ve...

Page 32: ...d in any low or high areas adjust the amount of river glass to correct gas flow Transformez votre cheminée et attendez environ 10 15 minutes jusqu à ce que les flammes sont une belle couleur jaune Notez la forme de la flamme et dans tous les domaines à basse ou haute ajuster la quantité de verre rivière pour corriger débit de gaz WARNING AVERTISSEMENT YOU MUST WEAR FLAME AND HEAT RESISTANT GLOVES ...

Page 33: ...r broken it is highly recommended that you contact a qualified service person Remove the broken pieces be sure to wear gloves and remove door See the replacement parts list at the end of the manual you will require one 5 mm ceramic glass panel with gasket installed Lay in a blob of high temperature silicone in each of the four corners of the door Then follow the instructions above to re install th...

Page 34: ...bas sur l écran afin de s aligner avec les dentelures de profondeur sur le support Voir l image ci dessous PINS Picture shown is looking at the left side of the fireplace and illustrating the screen bracket depth serrations mounted on pins WARNING AVERTISSEMENT Do not operate this appliance with the glass front removed cracked or broken Replacement of the glass should be done by a licensed or qual...

Page 35: ...ome yellow Visually check the flame after warm up Parfois après un démarrage à froid la vapeur peut se condenser et voiler le verre et les flammes peuvent être partiellement bleu Après quelques minutes l humidité disparaît et les flammes deviendront jaunes Contrôler visuellement la flamme après l échauffement 3 3 8 PILOT FLAME ADJUSTMENT For proper operation the pilot and main burner flames must b...

Page 36: ...isting burner orifice with a smaller size for installations over 4500 feet 1372m For the USA de rate the unit from sea level according to the gas installation code Toutes les vannes ont été pré set et certifié pour l installation à une altitude de 0 à 4500 pieds 0 1372m au dessus du niveau de la mer L appareil est certifié à la norme CSA 2 17 M91 appareils à gaz pour une utilisation à haute altitu...

Page 37: ...irer les panneaux d accès une de chaque côté de la zone pilote 4 The fan is attached with magnets for ease of installation and can be pulled off the rear wall Les fan sont attachés avec des aimants pour la facilité d installation et peut être retiré de la paroi arrière 5 Once removed from the wall the fan will slide out through the opening Une fois retiré du mur que les fan vont glisser par l ouve...

Page 38: ...SED CERTIFIED GAS INSTALLER TURN LE PRINCIPAL GAZ ET MISE HORS TENSION AU FOYER AVANT DE COMMENCER TOUT TRAVAIL SUR LA FOYER CELA DEVRAIT ETRE FAIT PAR UNE LICENCE VOTRE FOURNISSEUR DE GAZ 1 Remove the front access panel from below the door Remove the door as in 3 3 5 Retirez le panneau d accès avant d en bas de la porte Enlevez la porte comme dans 3 3 5 2 Undo the screws on the valve mount bracke...

Page 39: ...riaux combustibles essence et autres vapeurs et liquides inflammables 4 2 RECOMMENDED SERVICE SERVICE RECOMMANDÉ 1 The venting system should be annually inspected by a qualified agency Le système de ventilation devrait être inspectés annuellement par une agence qualifiée 2 Visually check the burner and pilot flames occasionally Visually inspect height and color of flames Contrôler visuellement le ...

Page 40: ... orifice du brûleur est propre Inspectez visuellement le pilote Brossez ou soufflez la poussière les peluches ou les débris étrangers Si l orifice pilote est branché le démontage peut être nécessaire pour éliminer toute matière étrangère de l orifice ou un tube Lorsque l appareil est remis en service vérifier le modèle flamme de la veilleuse Pour ré éclairage reportez vous aux instructions d éclai...

Page 41: ... spark at electrode weak or not heat source for pilot ignition 1 Improper ignition 1 Align the electrode with 1 8 3mm gap to pilot hood 2 Poor connections at starter and ignition electrode 2 Reconnect if loose 1 Broken ceramic cover on ignition electrode 3 Replace pilot assembly 2 Battery power low or dead 4 Replace batteries B No gas or low gas pressure 5 Gas line shut off s may not be turned on ...

Page 42: ...Clean air inlets 2 Vent system is restricted or inadequate 2 Confirm venting termination are those which are approved with the appliance 3 Logs are sooting up 3 Check manual for correct log placement V Flame burns blue and lifts off burner 1 Insufficient combustion air being supplied 1 Ensure that no foreign material blocks air inlets Ensure the vent is adequate 2 Manifold pressure set too high 2 ...

Page 43: ...45 x2 N A Orifice LP MP0505 56 x2 N A Propane Conversion Kit LPCKLCF65 CSA C US Natural Gas Conversion Kit NGCKLCF65 CSA C US Intermittent Pilot Remote Control Valve Parts Description Part Pilot Assembly Intermittent PSE NA291 CSA UL Valve AF 40004 CSA C US Valve with step motor installed AF 4044 CSA C US Remote Step Motor for AF 4000 Valve AF 4000MOT CSA C US Supreme Control Module incl wire harn...

Page 44: ...ay not be extended whatsoever by any of our representatives A licensed authorized service technician or contractor must have installed the gas fireplace Installation must be done in accordance with the installation instructions included with the product and all local and national building and fire codes This limited warranty does not cover damages caused by misuse lack of maintenance accident alte...

Page 45: ...ame sont conçus avec des composants et des matériaux de qualité supérieure assemblés par des artisans qualifiés qui sont fiers de leur travail Le brûleur et la valve sont des essais d étanchéité et d essai ont tiré sur un poste de contrôle de qualité Une fois assemblé chaque foyer est soigneusement inspecté par un technicien qualifié avant l emballage afin de s assurer que vous le client reçoit le...

Page 46: ...emière année Sierra Flame peut à sa discrétion se décharger de toutes obligations à l égard de cette garantie en remboursant à l acheteur d origine le prix de gros de toute pièce garantie qui est défectueuse s Nonobstant toutes dispositions contenues dans la présente garantie Sierra Flame responsabilité en vertu de cette garantie est définie comme ci dessus et il ne doit en aucun cas s étendre à d...

Page 47: ...Page 47 of 54 8 0 LABEL INFORMATION ...

Page 48: ...ve the grounding prong from this plug AVERTISSEMENT Instructions à la terre électrique Cet appareil est équipé d un à trois broches terre pour votre protection contre les risques de choc électrique et doit être branché directement dans une prise à trois broches récipient Ne pas couper ou retirer la broche de terre de cette fiche This appliance must be properly connected to a venting system in acco...

Page 49: ...Page 49 of 54 APPENDIX A AMERICAN FLAME VALVE INFORMATION ...

Page 50: ...Page 50 of 54 APPENDIX A Continued ...

Page 51: ...h is in the ON position and the appliance ON OFF switch is turned on the pilot will spark and light When the appliance ON OFF switch is turned to OFF the pilot will stay ON when the main burner shuts off This setting is generally used in cold climates to keep the firebox warm d The Continuous Pilot mode can also be activated by an optional hand held remote control 2 Remote Control Feature The AF 4...

Page 52: ...r propane Each unit leaves the factory equipped for one specific fuel but it is simple to field convert the unit to an alternate fuel The original type of fuel is marked on the ratings label of the manual Les modèles Elite sont conçus pour brûler du gaz naturel ou au propane Chaque unité quitte l usine équipée pour un combustible spécifique mais il est simple de convertir aligner l appareil à un c...

Page 53: ...ical power before proceeding with the conversion ATTENTION l alimentation en gaz doit être coupée avant de débrancher l alimentation électrique avant de procéder à la conversion 2 Remove the door rock glass kit and burner Retirez les portes rock kit de verre et le brûleur 3 Change the burner pilot orifices with the orifice supplied by the manufacturer for propane or natural gas Changer le brûleur ...

Page 54: ...onsibility that the conversion has been completed properly as per instructions in this manual Cet appareil a été converti sur DATE _______________________________________ partir de NG LP pour LP NG PAR____________________________________________________________________________________________ avec le kit de conversion NGCKLCF65 ou LPCKLCF65 aussi clairement marqué sur le bas de la plaque l étiquet...