NAPCO Gemini C
-
Series Control Panel Programming Instructions
--
Volume 2
NAPCO Security Group
Programming Instructions, Volume 2
Page 79
ZONE OPTIONS / ZONES 1-8 (ADDRESS 2002-2088)
ZONE OPTIONS:
1.
Select the desired zone option by entering the option
number (1
-
8) for each selected zone.
2.
Enter corresponding option number in address location, in
Binary (Bit) Format.
3.
Press
U
to save.
NOTE:
Dark shaded data value box shows option not avail-
able.
ZONE OPTIONS
ADDR
ZONES 1
► 8
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
1
2
3
4
5
6
7
8
Zone Area 1 (Fire)
2044
Zone Area 2
2045
Zone Area 3
2046
Zone Area 4
2047
Zone Area 5
2048
Zone Area 6
2049
Zone Area 7
2050
Zone Area 8
2051
Reserved
2052
Reserved
2053
Zone Anding Group 1
2054
Zone Anding Group 2
2055
Zone Anding Group 3
2056
Zone Anding Group 4
2057
Zone Anding Group 5
2058
Zone Anding Group 6
2059
Zone Anding Group 7
2060
Zone Anding Group 8
2061
Interior 1 Bypass
2062
Interior 2 Bypass
2063
Keypad Sounder on Alarm 2064
Ext Fire Output 1
2065
Ext Fire Output 2
2066
Ext Fire Output 3
2067
Ext Fire Output 4
2068
Ext Fire Output 5
2069
Ext Fire Output 6
2070
Ext Fire Output 7
2071
Ext Fire Output 8
2072
Reserved
2073
Reserved
2074
Carbon Monoxide
2075
Verification (Fire)
2076
Waterflow (Fire)
2077
Supervisory
2078
Monitor Zone
2079
NAC A
2080
NAC B
2081
NAC C
2082
NAC D
2083
Reserved
2084
Reserved
2085
Chime 2
2086
Delayed Trip 1
2087
Delayed Trip 2
2088
ZONE OPTIONS
ADDR
ZONES 1
► 8
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
1
2
3
4
5
6
7
8
Priority Zone
2002
Priority / Bypass
2003
AutoBypass
2004
Selective Bypass
2005
Keyswitch Arming
2006
AutoBypass Re-entry
2007
Pre-Alarm Warning
2008
Never Arm
2009
24-Hour Protection
2010
Burg Bell
2011
Pulse Burg Bell
2012
Burg PGM2
2013
Burg Relay
2014
Burg PGM1
2015
Exit/Entry #1
2016
Exit/Entry #2
2017
Exit/Entry Follower
2018
Auto Reset
2019
Swinger Shutdown
2020
Chime Zone
2021
Abort Delay
2022
Power-Up Delay
2023
Day Zone/Trouble Open 2024
Day Zone/Trouble Short 2025
Alarm on Day Zone/Trouble
2026
Report Alarm Tel1
2027
Rpt Alm Restore Tel1
2028
Report Trouble Tel1
2029
Rpt Tbl Restore Tel1
2030
Reserved
2031
Reserved
2032
Reserved
2033
Reserved
2034
Report Alarm Tel3
2035
Rpt Alm Restore Tel3
2036
Report Trouble Tel3
2037
Rpt Tbl Restore Tel3
2038
No EOL Resistor
2039
Sensor Watch
2040
Trouble on Open
2041
Trouble on Short
2042
Trouble on Night Open 2043
FOOTNOTES AND SYMBOLS FOR TABLES
A
2
-
wire smoke detectors only available for zones 1
-
8 or utilizing
FWC
-
FSLC
-
CZM on SLC loop. See Installation Instructions
(WI1653) for more details.
B
If
Fire Alarm Verification
is selected, then
Fire
must also be
selected.
C
When the Easy Program Menu is used, these features are
enabled by default (for new panels or after a Cold Start
(address 8179)). Zone Area 1 is enabled for the first 8 zones
only, by default.
D
Disable
Auto
-
Reset
on non
-
Fire zones for SIA CP
-
01 installa-
tions.