NAPCO Security Group
NAPCO Gemini C
-
Series Control Panel Programming Instructions
--
Volume 2
Page 80
Programming Instructions, Volume 2
ZONE OPTIONS / ZONES 9-16 (ADDRESS 2102-2188)
ZONE OPTIONS:
1.
Select the desired zone option by entering the option
number (1
-
8) for each selected zone.
2.
Enter corresponding option number in address location, in
Binary (Bit) Format.
3.
Press
U
to save.
NOTE:
Dark shaded data value box shows option not avail-
able.
ZONE OPTIONS
ADDR
ZONES 9
► 16
Z9
Z10
Z11
Z12
Z13
Z14
Z15
Z16
1
2
3
4
5
6
7
8
Zone Area 1 (Fire)
2144
Zone Area 2
2145
Zone Area 3
2146
Zone Area 4
2147
Zone Area 5
2148
Zone Area 6
2149
Zone Area 7
2150
Zone Area 8
2151
Reserved
2152
Reserved
2153
Zone Anding Group 1
2154
Zone Anding Group 2
2155
Zone Anding Group 3
2156
Zone Anding Group 4
2157
Zone Anding Group 5
2158
Zone Anding Group 6
2159
Zone Anding Group 7
2160
Zone Anding Group 8
2161
Interior 1 Bypass
2162
Interior 2 Bypass
2163
Keypad Sounder on Alarm 2164
Ext Fire Output 1
2165
Ext Fire Output 2
2166
Ext Fire Output 3
2167
Ext Fire Output 4
2168
Ext Fire Output 5
2169
Ext Fire Output 6
2170
Ext Fire Output 7
2171
Ext Fire Output 8
2172
Reserved
2173
Reserved
2174
Carbon Monoxide
2175
Verification (Fire)
2176
Waterflow (Fire)
2177
Supervisory
2178
Monitor Zone
2179
NAC A
2180
NAC B
2181
NAC C
2182
NAC D
2183
Reserved
2184
Reserved
2185
Chime 2
2186
Delayed Trip 1
2187
Delayed Trip 2
2188
ZONE OPTIONS
ADDR
ZONES 9
► 16
Z9
Z10
Z11
Z12
Z13
Z14
Z15
Z16
1
2
3
4
5
6
7
8
Priority Zone
2102
Priority / Bypass
2103
AutoBypass
2104
Selective Bypass
2105
Keyswitch Arming
2106
AutoBypass Re-entry
2107
Pre-Alarm Warning
2108
Never Arm
2109
24-Hour Protection
2110
Burg Bell
2111
Pulse Burg Bell
2112
Burg PGM2
2113
Burg Relay
2114
Burg PGM1
2115
Exit/Entry #1
2116
Exit/Entry #2
2117
Exit/Entry Follower
2118
Auto Reset
2119
Swinger Shutdown
2120
Chime Zone
2121
Abort Delay
2122
Power-Up Delay
2123
Day Zone/Trouble Open 2124
Day Zone/Trouble Short 2125
Alarm on Day Zone/Trouble
2126
Report Alarm Tel1
2127
Rpt Alm Restore Tel1
2128
Report Trouble Tel1
2129
Rpt Tbl Restore Tel1
2130
Reserved
2131
Reserved
2132
Reserved
2133
Reserved
2134
Report Alarm Tel3
2135
Rpt Alm Restore Tel3
2136
Report Trouble Tel3
2137
Rpt Tbl Restore Tel3
2138
No EOL Resistor
2139
Sensor Watch
2140
Trouble on Open
2141
Trouble on Short
2142
Trouble on Night Open 2143
FOOTNOTES AND SYMBOLS FOR TABLES
A
2
-
wire smoke detectors only available for zones 1
-
8 or utilizing
FWC
-
FSLC
-
CZM on SLC loop. See Installation Instructions
(WI1653) for more details.
B
If
Fire Alarm Verification
is selected, then
Fire
must also be
selected.
C
When the Easy Program Menu is used, these features are
enabled by default (for new panels or after a Cold Start
(address 8179)). Zone Area 1 is enabled for the first 8 zones
only, by default.
D
Disable
Auto
-
Reset
on non
-
Fire zones for SIA CP
-
01 installa-
tions.