8.0 POSITION OF WARNING LABEL
8.1 POSITION OF THE WARNING LABELS (Fig. 4)
The labels fitted on the compressor unit are part of the machine; they have been applied for safety purposes and must
not be removed or spoiled for any reason.
Ref.1 - Spare plate Code
1079 9903 48
8.2 POSITION OF THE DATA PLATES (Fig. 4)
2) “Compressed air inlet”
4) Identification plate
3) “Compressed air outlet”
9.0 INSTALLATION LOCATION
9.1 FLOOR
The floor must be level and be of a type that can suitably support the total weight of the machine as shown in Fig. 5
Remember the total weight of the machine when positioning it.
9.2 VENTILATION
The choice of an appropriate room will prolong the life of your dryer; the room must be spacious, dry, well ventilated and
free from dust.
The operating conditions to be complied with are the following:
Min. room temperature: 41 °F (5 °C) (compulsory)
Min. inlet allowed temperature: 37,4 °F (3 °C)
Max. room temperature: 113 °F (45 °C) (compulsory)
Max. inlet allowed temperature: 131 °F (55 °C)
Max. temperature of incoming air: 131 °F (55 °C)
Max. working pressure: 203 psi (14 bar)
Please keep environmental conditions stable (temperature and humidity) in order to avoid refrigerant compressor/fan
overload and/or reduction of dryer performance. Similar failures shall affect warranty reimbursements.
Please ensure the appropriate composition of the air within the machine room: - clean with no damaging contaminants
(e.g., dust, fibers, fine sand) - free of explosive or chemically unstable gases or vapors - free of acid/alkaline forming
substances, particularly ammonia, chlorine or hydrogen sulfide. Similar failures shall affect warranty reimbursements.
Please note that we do not recommend the use of ducting for the cooling air on these units.