Setting the service interval
To set the service interval, follow steps 1 to 9:
1. PDP is showing standard view.
2. Push and hold buttons SET (8) and DOWN (10) to enter the menu.
3. Message “SE” appears on display.
4. Push and release SET (8) to enter the “SE” menu.
5. Current service interval is displayed.
(“60” or any other value between “0” and “99”)
6. Select desired service interval using the UP and DOWN button.
(40=4000h, 55=5500h, 80+8000h,…)
7. Push and release SET to confirm the new service interval.
8. The selected value blinks during 3 seconds.
9. Then “rS” is fixed and “°C” blinks on display for about 10 seconds.
The new service interval is now set.
Freeze protection function
Once the digital controller detects a dewpoint temperature below -28,4°F (-2°C) lasting for more than 2 minutes,
(L2 Alarms), it switches off the refrigerant compressor.
Resetting the dryer after a refrigerant compressor stop
Press button 7 to reset the alarm.
The dryer restarts when both the following conditions are true.
•
The dewpoint temperature is higher than -2°C
•
30 second are passed from the refrigerant compressor stop (minimum balancing pressure stop time).
A countdown is available if the reset is made before the minimum stop time.
Silent alarm function
To snooze the alarm, press button 7.