16.0 ROUTINE MAINTENANCE
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE DISCONNECT IT FROM THE POWER
SOURCE AND ISOLATE THE UNIT FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
16.1 MAINTENANCE SCHEDULE
These maintenance intervals are recommended for work environments that are not dusty and are well ventilated. For
particularly dusty environments, double the frequency of the recommended service intervals.
Every week
Brush/blow off the finned surface of the condenser
Clean the filter of the automatic condensate drain
Every 2000 hours / 1 year
Replace the filter of automatic condensate drain (2902016102)
Every 4000 hours / 2 year
Replace drain kit (2200902017)
16.2 CLEANING OF THE AUTOMATIC CONDENSWATER DISCARGER FILTER (Fig. 10)
Clean the filter of the drain.
Proceed as follows:
- Isolate the unit from the compressed air network Ref. 1 Fig. 10
- Remove the panel Ref. 5 Fig. 10
- Release the pressure in the dryer by pressing the condensate drain “TEST” button locate on the
drain
Ref. 2 Fig. 10.
- Switch off the machine. Turn the switch in position STOP Ref. 3 Fig. 10.
- Lock-out and tag-out the unit at the fuse/breaker box.Ref. 4 Fig. 10
HOT PARTS INSIDE
- Remove the Y-strainer plug Ref. 6
- Remove the filter Ref. 7
- Clean the filter Ref. 7 with a jet of air, working from inside to outside
- Re-Install the filter, fix the plug Ref. 7 - 6
- Close the panel Ref. 5