APPENDIX A  

NANAWALL WD66 OWNER’S MANUAL

GLASS INSTALLATION AND GLAZING 

This section applies only if you need to install glass for 
any reason or if glass setting blocks need to be adjusted. 
Proper glass installation is critical, as, with the NanaWall 
folding system, glass is a structural part of the panel. 

Glass stops and glazing gasket are to be used for “dry”

 

glazing of each panel. Also needed are setting blocks.

 

Use glass setting blocks with varying thickness made

 

from hard plastic. Rubber setting blocks are not

 

acceptable. Width of setting blocks should be at least

 

1/8

"

 

wider than

 

the glass thickness and 1/16

"

 to 1/8

"

 less

 

than

 

the width of the glazing pocket. 

Glass, with appropriate dimensions, thickness and 
specifications will be needed. Depending on the model, 
widths of all glass panels may not be equal. Please note 
that glass is required to be fully tempered unless the unit 
is a window placed above a certain height from the floor. 
Check with all applicable codes and regulations. 

Float glass, including the glass components of insulated 
glass, shall meet the current requirements of ASTM C 
1306 “Standard Specifications for Flat Glass” for quality, 
thickness and dimensional tolerances. Tempered float 
glass shall meet the current requirements of ASTM C 
1048 “Standard Specifications for Heat-Treated Flat 
Glass - Kind HS, Kind FT Coated and Uncoated Glass.” 
All tempered glass shall have a permanent logo, which 
signifies Safety Commission 16 CFR-1201 and the safety 
glass test requirements of ANSI Z 97.1 (current editions). 
Insulating Glass shall meet the requirements of ASTM E 
774, Class A, B or C. 

Although glass installation with the “dry” glazing system 
is relatively straight forward, it is recommended that an 
experienced glazing contractor be used. 

It is 

very important 

that the bracing direction and 

placement of glass setting blocks on opposite diagonal 
corners be correct. Setting blocks are to be placed only 
at opposite diagonal corners with corners alternating with 
each succeeding panel. This is necessary for the stability 
and balance of the panels when in operation. If not 
correctly braced, the unit will not operate properly. 

The general rules for bracing are as follows:

• For a panel attached to a side jamb, the lower brace

should be at the lower corner closest to the side.

• For a panel with a running carriage, the lower brace

should be on the lower corner that is on the same
side as the running carriage.

• For a swing panel, the lower brace should be at the

lower corner away from the stile with the locking
hardware. See Diagram 1 for an example of setting
block locations.

Follow all proper applicable glass installation and glazing 
techniques as recommended in the Flat Glass Marketing 
Association (FGMA) “Glazing Manual” and “Sealant 
Manual”. Always use suction cups to shift glass within an 
opening. It would be best to install the glass on the panels 
before they are installed in the opening. Panels can be laid 
flat on sawhorses. If the panels are already installed, they 
can still be glazed.

1.

Close all panels and secure them with the multiple
point lock bolts. Start with a panel that is attached to
a side jamb or, in the case of unhinged pairs, closest
to a side jamb.

2. Remove all glass stops on the panel. Be sure to

protect the finish.

Содержание WD66

Страница 1: ...6 Standard Wood Framed Folding System This manual is to be used by the installer for installation and is to be kept by the Owner for reference Replacement parts can be ordered directly through NanaWal...

Страница 2: ...However not included are screws bolts shims etc to anchor the unit to the rough opening The frame is shipped knocked down and needs to be assembled Panels are pre assembled with or without glass read...

Страница 3: ...e frame height of the unit ordered is measured from the bottom of the sill and not from the finished floor Allowance must be made in height for the portion of the sill that is below the measured openi...

Страница 4: ...protection any exterior folding system should be installed under an overhang or with other similar protection 7 For better performance it is recommended that all dead loads such as upper levels roof...

Страница 5: ...stomer s specific application requirements can be evaluated Your local paint professional should know of suitable finish systems that give satisfactory results in your region It is highly recommended...

Страница 6: ...stainless steel insert for the sill of floor supported WD66 u are in the correct place Illustration A1 Step A3 For top hung WD66 o L R with unhinged pairs of panels not connected to a side jamb see St...

Страница 7: ...c surrounding conditions must be properly designed and provided by others Drawings not to scale Details shown are subject to change without notice INWARD OPENING DETAILS OUTWARD OPENING DETAILS TOP HU...

Страница 8: ...s or other equivalent anchorage devices depending on the adjacent substrate material and construction Make sure they are corrosion resistant Anchorage devices should penetrate or hold sufficiently INW...

Страница 9: ...of 3 200 psi use 3 16 diameter ITW Tapcons concrete screws with 1 1 4 min embedment For masonry use 1 4 diameter ITW Tapcons masonry screws with 1 1 4 embedment Standard installation into light gage s...

Страница 10: ...nd free of any debris especially cuttings from drilled holes See Illustration A3 B PANELS AND FOLDING HARDWARE INSTALLATION IMPORTANT Look for glass stops to determine the interior side of a panel Ste...

Страница 11: ...t secures the assembly See also Illustration B3 Step B6 Attach the next panel to this folding pair by demounting the long screw of the running carriage that way that the hinge part of the next panel c...

Страница 12: ...panel If it is slightly lower not more than 1 16 it is okay Then along the entire width of the opening check the spacing between the sill and each panel which should be about 3 8 along the entire leng...

Страница 13: ...ep C11 Finish any waterproofing flashing trim and sealant needed around the perimeter of the opening Important Make sure any weep holes in the sill are not blocked Step C12 To prevent uncontrolled mov...

Страница 14: ...curity and weather resistance When closed please engage all locking mechanisms fully The correct sequence of opening and closing of panels is dependent on the configuration ordered Panels must be open...

Страница 15: ...side or a thumb turn on the inside Unlock and disengaging the locking points Unlock the lock with key or thumb turn By operating the door handle downwards the locking points at the top and the bottom...

Страница 16: ...al loading and forced entry 5 Periodically inspect the sealant caulking on the exterior perimeter of the unit It is extremely important that the sealant caulking remains intact and in good condition T...

Страница 17: ...jamb tracks should be free from all dirt and debris c There should be no standing water in the track in the sill d All hardware should be intact and operating properly 2 All surfaces must be cleaned w...

Страница 18: ...Insulating Glass shall meet the requirements of ASTM E 774 Class A B or C Although glass installation with the dry glazing system is relatively straight forward it is recommended that an experienced...

Страница 19: ...pry bar at the lower corner below the upper setting block These setting blocks should all fit snugly but should not be forced Adjust the thickness of the glass setting blocks such that the panel is sl...

Страница 20: ...ls have to be braced correctly for proper operation DIAGRAM 1 Setting blocks for tension Setting blocks to keep distance B r a c i n g D i r e c t i o n B r a c i n g D i r e c t i o n B r a c i n g D...

Страница 21: ...must be provided 3 Inward opening details are shown on this drawing Outward opening panels require the same installation fasteners at the same spacings 4 Installation fasteners shown in the raised si...

Страница 22: ...antial cracking chipping or peeling due to the deterioration of the finish exclusive of mechanical damage 2 chalking in excess of a numerical rating of 8 as per ASTM D 659 or 3 fading or color changes...

Страница 23: ...e of the affected product in full satisfaction of its obligations Wood Wood components must be properly finished on all sides promptly after receipt of unit before installation of unit and prior to ex...

Страница 24: ...Product selection application storage handling modification or waterproofing Movement of surrounding substrates including deflection of the header of more than or any other stresses on product Instal...

Страница 25: ...faces Acts of God falling objects fire accidents external forces or other conditions beyond NanaWall s control Gas fill or retention levels in insulated glass units Field testing of Product Performanc...

Страница 26: ...___________________________________ Project Address if different from above _____________________________________________________________ INSTALLATION Installer Name _______________________________ Ad...

Отзывы: