background image

  

13 of 32

www.NabcoEntrances.com

SwingandFoldDoorOpusControlWiringandProgrammingInstallationManual

Rev. 8-11-21 

P/N C-00139

Base Setting

Setting Category

Menu Item

Default

Action

Door Hand

(for Fold Doors)

Left

Right

Left

From the Exterior Side of Building, determine which Handing to 

enter: Left or Right

DN 0833

EXTERIOR BREAKOUT SIDE

LEFT HAND

RIGHT HAND

Encoder

(For Swing Doors)

Yes

No

Yes

No if an Encoder not used.

SECTION 8.2: Movement Settings

Movement Setting

Parameter

Range

Default

Description

Open Speed

0 - 7

3

The higher the number the faster the Door opens

Back Check Speed

0 - 7

3

Sets door speed during Back Check

Back Check Range

0 - 7

3

Swing Door: 2-1/2° to 35° of Fully Open

Close Speed

0 - 7

3

The higher the number the faster the Door closes

Latch Check Speed

0 - 7

3

Sets door speed during latch check

Latch Check Range

0 - 7

3

Swing Door: 10° to 45° of Fully Closed

Open Timer

0-10, 12, 15, 

 

20, 25, 30

2

Hold Open time after Door reaches Full Open and activation signal is no 

longer present.

Reaction Power

0 - 7

3

Determines how fast the door reacts to a reactivation when closing.

Open Recycle Sens

0 - 7

3

Recycle detection Sensitivity. Determines how much force is exerted during 

opening or closing cycle.

“0”= most sensitive

“7” = least sensitive

Close Recycle Sens

After Open Recycle

Slow Open

Slow Open Determines what happens after a recycle during Opening cycle.

Slow Open = Door stops then slowly opens.

Stop = Door stops then slowly closes.

Stop

Close Recycle

Reopen

Yes

Yes

Determines what happens after a recycle while closing cycle.

Yes = Door re-opens

No = Door stops then slowly closes

No

SECTION 8.3: Optional Settings

Optional Setting

Parameter

Range

Default

Description

Hold Close Force

0 - 3

0

0

OFF

3

Strongest Hold Close force

Power Close Range

No Power Close

No Power Close Closing assisted by Motor to fight wind or stack pressure

Whole Close Cycle
Latch Check Only
Latch and Back

Manual Open Function

No Action

No Action

Does nothing

Push and Go

P & G Enables push and go

Stop and Close

S & C Door pauses at open angle then closes

Содержание C-00139

Страница 1: ...N 2 4 QR Code Links 4 CHAPTER 3 GETTING STARTED 5 SECTION 3 1 Features 5 SECTION 3 2 Wiring 5 SECTION 3 3 General Specifications 5 SECTION 3 4 Electrical Specifications 5 SECTION 3 5 Output Power Guid...

Страница 2: ...gs 18 CHAPTER 10 SHUT OFF CIRCUIT BREAKER 19 CHAPTER 11 SWING DOOR WIRING DIAGRAMS 19 SECTION 11 1 120 VAC General Wiring 19 SECTION 11 2 Motor Wiring 20 SECTION 11 3 Other 20 SECTION 11 4 Activation...

Страница 3: ...isconnect all power to the junction box prior to making any electrical connections Failure to do so may result in serious personal or fatal injury When uncertain whether power supply is disconnected a...

Страница 4: ...be installed within new Swing Sliding and Folding Door Units plus X Existing swing sliding and folding doors using Analog Magnum or U01 U19 controls works with encoders or microswitches X Existing sl...

Страница 5: ...cation Description Temperature Range 13 degrees to 140 degrees Fahrenheit Motor Type High voltage Brushless Motor with Encoder 115V Number of Signal Inputs 1 x Activation 2 x Door Mode 2 x Safety 1 x...

Страница 6: ...mA 50 mA Total 350 mA 350mA does not exceed total current draw An Auxiliary Power Supply does not need to be used SECTION 3 6 The Opus Control for Swing Doors Note The Hold Close feature is enabled w...

Страница 7: ...TION 3 10 CAN Bus Communication Used to connect Sim Pair Astragal Sequencing and the NET HT Cable when programming CHAPTER 4 LCD CATEGORY SCREENS Passcode Go to Se ng Menu Stroke Learning Yes No UNIT...

Страница 8: ...se refer to Subsection Table 5 The screen above shows the Opus control installed on a GT710 X Error Specifications This screen will only display an Error Code in the event there is an Error Otherwise...

Страница 9: ...eset to Default Set If you don t know the passcode Keep Pushing Switch Return to Normal mode 0 0 Short Push Reset to Default Set If you don t know the passcode Keep Pushing Switch Return to Normal mod...

Страница 10: ...data Since monitored sensors are only connected to one control Type 2 you don t want the monitoring settings to be copied to the control without sensors connected Type 1 Any changes to one control suc...

Страница 11: ...Rotary Dial Enter the passcode 0045 1 Turn the Rotary Dial clockwise to highlight a preferred number then briefly press down 2 Repeat until the passcode is complete 4 Briefly press down on the Rotary...

Страница 12: ...lly need to be copied are already established X Door mounted safety sensors should be connected to the control running the door which those sensors apply to X When monitored sensor wiring is different...

Страница 13: ...Open time after Door reaches Full Open and activation signal is no longer present Reaction Power 0 7 3 Determines how fast the door reacts to a reactivation when closing Open Recycle Sens 0 7 3 Recycl...

Страница 14: ...9 Latch Check LCHK Lockout Angle Back Check BCHK Lockout Angle Available Angle Con nuous Safety Available Angle for Low Energy Door Mount Approach Side Sensor Available Angle Safety with lockout Avail...

Страница 15: ...happened Output closes when recycle occurs Electric Strike Lock Set for electric strike functionality N O Electric Magnetic Lock Set for Mag lock functionality N C Air lock Set for Air lock functional...

Страница 16: ...ock if equipped Hold Open Mode Holds door in open position Asia Only Do Not Use ANSI does not allow Activation Sensor to be mounted on the swing side of door If activated Opus will ignore the Activati...

Страница 17: ...not operating until the problem is fixed Monitoring settings are OFF by default except when used as 1175 Opus Slide in which case standard settings have monitoring enabled SECTION 8 6 History Setting...

Страница 18: ...tary Dial 2 Sec 11 20 10 12 Enter Passcode 0045 Clear Recycle Cnt 0045 If you don t know the passcode Keep Pushing Switch Return to Normal mode 11 20 10 12 LEVEL 4 1 Rotate Dial to select History Se n...

Страница 19: ...the grounding screw or grounding wire whichever is provided Attention Insert all Incoming 120 VAC Power wires into the pre drilled Electric Service Access Hole located at the left or right side of He...

Страница 20: ...tor Fuse SECTION 11 3 Other DN 1333 EXAMPLE OF A PROGRAMMABLE INPUT I O Terminal 8 14 8 BA Breakout Used mainly for sliding door can be used for ON OFF with Swing Doors 9 SQ Sequen al Ac va on Signal...

Страница 21: ...DER RADIO RECEIVER ETC WARNING TOTAL POWER OF ALL SENSORS AND POWERED ACTIVATION DEVICES MUST NOT EXCEED 750 MA POWERED ACTIVATION DEVICES Radio Receiver DN 1329 8 12 14 11 13 9 10 N O COM N O COM Ext...

Страница 22: ...ensor Card Reader Radio Receiver etc WARNING TOTAL POWER OF ALL SENSORS AND POWERED ACTIVATION DEVICES MUST NOT EXCEED 750 mA NON POWERED ACTIVATION DEVICES Radio Receiver 8 Rocker Switch P N A 00805...

Страница 23: ...ation Manual Rev 8 11 21 P N C 00139 SECTION 11 6 Safety without Monitoring DN 1331 2 4 5 1 6 N O COM PWR PWR N O COM PWR PWR N O COM PWR PWR Door Mounted Approach Side Sensor Door Mounted Swing Side...

Страница 24: ...t be set to BODYGUARD OUTPUT Please see programming instruc ons for details PWR PWR TEST TEST Door Mounted Approach Side Sensor N O COM PWR PWR TEST TEST N O COM PWR PWR TEST TEST 5 2 4 5 1 2 3 4 6 7...

Страница 25: ...DN 1332 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Fail Secure Electric Strike Fail Secure Lock Shown Fail Safe and Mag Locks will use N C instead of N O Power Supply For Electric Strike N O COM N C Varistor M...

Страница 26: ...P N A 00805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used WARNING TOTAL POWER CONSUMP...

Страница 27: ...SENSORS MUST NOT EXCEED 750 MA N O COM PWR PWR N O COM PWR PWR N O COM PWR PWR COM PWR PWR N O Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor 5 2 4 1 2 3 4 6 7 1 5 8 12 14 11 13 9 10...

Страница 28: ...P N A 00430 Clear A 70430 Dark Bronze RED BLACK 14 13 12 11 10 9 8 8 WHITE Off Hold Open On Off 14 13 12 11 10 9 8 8 14 BA break out input must be set to N C on the Opus Control is by default Panic L...

Страница 29: ...OCK OPEN DELAY TIMER must be set to an appropriate me for the door to unlock before opening LOCK CONDITION must be set to ONE WAY NIGHT ONLY NOTE If the Rocker Switch is not being used Interior Ac va...

Страница 30: ...connected Type 1 Any changes to one control such as speed or timing should be entered on the other control manually not copied SECTION 12 1 Switches and Sensors with Monitoring DN 1895 Approach Side A...

Страница 31: ...Latch Check Software Revision up to and including 19 Symptom When the door is used manually it closes every time However when the door is activated once in a while it will stop at latch check and not...

Страница 32: ...rror MPU Clock error MPU Interrupt error MPU SW reset error MPU HW WDT error MPU EEPROM error No Motor Motor disconnection error Check all connections between the Control and Motor Thrml Warning Therm...

Отзывы: