background image

 

 

12 

 

5.

 

INSTALATION 

5.1

 

Electrical connection 

Check that the voltage at the point where the furnace is to be connected matches the 
operating voltage of the equipment. 

Before carrying out any electrical work, make sure that there is no electric current at the 
equipment connection point. 

The  equipment  must  be  connected  to  the  mains  by  means  of  an  omnipolar  cut-off 
switch and with a contact opening distance of more than 3 mm. Also install a class A 
differential device and overcurrent protection. 

Always guarantee an efficient earthing system. 

Connect  the  equipment  to  an  equipotential  bonding  system 

using  the  specially 

designed contact for this purpose (see equipotential sign on the lower left side of the 
equipment).  In  the  case  of  two  stacked  equipment,  both  must  be  connected  to  the 
equipotential bonding system. 

 

Connection to an equipotential bonding system ensures additional safety in 
the event of simultaneous ground fault and differential failure. 

Wiring  and  other  safety  devices  used  for  electrical  installation  must  have  the 
appropriate cross-section for the equipment in question. 

 

Observe the applicable regulations for connecting the equipment to the low-
voltage mains supply. 

Before starting the electrical installation, verify that the electrical requirements of the 
furnace and mains supply are the same.  

For correct connection after positioning, you will need a cable with a length that allows 
you  to  reach  the  connection  point  plus  about  20cm,  to  make  the  connection  on  the 
back  of  the  equipment.  Remove  the  rear  plate  from  the  equipment.  Insert  the  cable 
through the cable gland in the lower left-hand side of the furnace (see rear panel).  

Some MyChef ovens can be connected to different voltages and configurations at the 
time of installation. To make the correct connection, use the terminal blocks supplied 
with the equipment according to the instructions in the following subchapters. These 
terminal strips are located between contacts 4 and 5 of the terminal block. 

 

Содержание 10GN 1/1

Страница 1: ...COMBI OVEN INSTALLATION MANUAL ...

Страница 2: ...ard 8 3 4 Corrosion hazard 8 4 RECEPTION TRANSPORT AND POSITIONING 10 4 1 Reception 10 4 2 Transport 10 4 3 Positioning 10 5 INSTALATION 12 5 1 Electrical connection 12 5 1 1 Three phase connection 400V 3L N 14 5 1 2 Three phase 230V 3L 15 5 1 3 Single phase 230V L N 17 5 2 Water connection 19 5 2 1 Water input 19 5 2 2 Drain 19 5 3 Vapour condensation hood 19 6 GENERAL ELECTRICAL DIAGRAM 21 6 1 P...

Страница 3: ... the necessary skills or experience for the correct operation of the equipment Do not allow children to use or play with the computer The owner of the equipment has the obligation to have this manual read to the personnel in charge of its use and maintenance and to keep this manual in a safe place so that it can be used by all users of the equipment and for future reference If the equipment is sol...

Страница 4: ...le section 2 5mm2 2 5mm2 2 5mm2 2 5mm2 2 5mm2 Table 1 Main features of MyChef S ovens The maximum recommended load of food per GN 1 1 40mm tray is 3 5 Kg and 2Kg for GN 2 3 trays 2 2 Main characteristics MyChef L 6GN 1 1 6GN 2 1 10GN 1 1 10GN 2 1 External dimensions Width x Depth x Height 760 x 700 x 822mm 760 x 950 x 822mm 760 x 700 x 1122mm 760 x 950 x 1122mm Capacity 6 GN 2 3 40mm 6 GN 1 1 40mm...

Страница 5: ...isconnect the cables and drains and water pipes 3 3 Thermal hazard When the appliance is in operation open the door slowly and carefully to avoid possible burns from the steam or hot air that may come out of the cooking chamber Keep ventilation openings clear of obstacles Do not install the equipment in the vicinity of flammable products Avoid positioning the oven near sources of heat such as stov...

Страница 6: ...r spray masks and chemical protective gloves MyCare cleanduo and DA21 cleaning products have been specially formulated for the correct cleaning and protection of MyChef ovens with automatic and semi automatic washing respectively Both products contain in addition to detergent polish for a perfect finish The use of these detergents in MyChef ovens is mandatory Use MyCare cleanduo in ovens equipped ...

Страница 7: ...s properly installed and operating To move the equipment and place it in your workspace consider the following observations The dimensions of the different models to be taken into account when passing through narrow spaces passageways doors narrow spaces See Table 1 and Table 2 The manipulation must be done with the necessary personnel to move the load of the furniture taking into account the regu...

Страница 8: ...must be at a distance of more than 1 metre Once it is placed in the workspace check that it is level Never block the underside of the front water collector Figure 1 Example of suitable installation location For the installation of stacked MyChef ovens follow the instructions supplied with the corresponding stacking kit 500m m 100mm 50mm 1000m m 50mm ...

Страница 9: ... the event of simultaneous ground fault and differential failure Wiring and other safety devices used for electrical installation must have the appropriate cross section for the equipment in question Observe the applicable regulations for connecting the equipment to the low voltage mains supply Before starting the electrical installation verify that the electrical requirements of the furnace and m...

Страница 10: ...as been made that no cable is loose and they are all firmly fastened Also secure the cable gland Never connect a phase to neutral or ground Check that the installation voltages correspond to those of the equipment The following subchapters show the three types of possible connections for MyChef ovens ...

Страница 11: ...ase connection 400V 3L N Figure 4 Three phase 400V 3L N Figure 5 Three phase 400V 3L N Color Cable Connector Brown L1 1 Black L2 2 Grey L3 3 Blue Neutral 4 Green yellow Ground Ground Table 3 Three phase cable 400V 3L N ...

Страница 12: ...hase 230V 3L Figure 7 Three phase 230V 3L Color Cable Connector Brown L1 1 Black L2 2 3 Grey L3 4 Green yellow Ground Ground Table 4 Three phase cable 230V 3L MyChef To connect terminal block positions 2 3 use the connecting plate supplied with your MyChef oven ...

Страница 13: ...se 230V 3L Cable Cable Connector Brown L1 1 Black L2 2 4 Grey L3 3 Green yellow Ground Ground Table 5 Three phase cable 230V 3L MyChef L In this type of connection the triangular convection resistors must be rewired Delta Figure 10 Star and triangle Delta connections ...

Страница 14: ...0V L N This type of connection is only valid for MyChef ovens S 4GN1 1 and MyChef S 6GN2 3 Figure 11 Single phase half power Figure 12 Single phase half power Figure 13 Single phase full power Figure 14 Single phase full power ...

Страница 15: ... Blue Neutral 4 Green yellow Ground Ground Table 6 Single phase cable 230V L N Use the connecting plates supplied with your MyChef furnace to connect positions 1 2 and 2 3 of the terminal block 1 Connection in position 3 is made at full power ...

Страница 16: ... If it is a new installation the water should be allowed to run until the connection is completely purified This operation must be repeated each time work or repairs are carried out on the water supply to the furnace 5 2 2 Drain For proper operation of the steam system of the furnace the equipment must be connected to a drainage system of 40mm nominal diameter DN40 through a heat resistant pipe Th...

Страница 17: ...20 The steam condensing hood is optional equipment The hood can be installed after the furnace has been installed ...

Страница 18: ...21 6 GENERAL ELECTRICAL DIAGRAM 6 1 Power MyChef S Figure 16 Electrical drawing MyChef S ...

Страница 19: ...22 6 2 Relés MyChef L Figure 17 Electrical drawing MyChef L ...

Страница 20: ...23 6 3 Control MyChef S and MyChef L Figure 18 Human interface ...

Отзывы: