background image

10

COMMISSIONING AND ANNUAL MAINTENANCE TESTING

On commissioning carry out the following checks and tests:

• 

All the pipe work has been flushed through before fitting the valve 

• 

The valve you have purchased matches the installation 

• 

The supply pressures and temperatures are checked and all are in the range  

 

 

specified in the instructions

• 

The isolation valves and strainers are fitted and clean of any unwanted material and do

 

not restrict flow

Ensure both isolation valves are fully open. Turn the temperature control to cold and turn the 

flow on. Check the temperature is at the required minimum. Rotate the temperature controller 

gradually until it reaches the preset stop let it flow until the hot water has reached the valve and 

the temperature has stabilized. Check the temperature is 38˚C =/-2˚C. This is the valves factory 

preset.  

Note: 

If your temperature is not 38˚C the following operation should only be carried  

 

 

out by a competent TMV engineer. To adjust the temperature at the stop to 38˚C,    

 

this can be achieve by the following;

Firstly position the temperature control knob at the stop. Remove the temperature control knob 

by undoing the grub screw. Then turning the splined shaft clockwise to decrease the temperature 

(colder) or anti-clockwise to increase the temperature (hotter) when you have achieved a 

temperature of 38˚C, re-assemble the temperature control knob.

Override the stop by pressing the button and rotate to maximum being careful to avoid scalding. 

Measure the temperature.

The valve should then be checked to confirm the water isolation performs correctly. Run the 

valve at the 38˚C stop position. Check the water temperature. Turn off the feed of cold water 

using the isolation valve. The water flow should fall to a very low flow, (possibly only a drip) after 

a few seconds. Collect the water after 5 seconds and 30 seconds and measure the temperature 

it should be below 46˚C +/- 2˚C . Turn on the cold water again and it should return after a few 

seconds to stabilise to 38˚C +/- 2˚C.

Adjustment of the temperature settings is only to be carried out by a competent TMV engineer 

as it is a technically difficult operation in which the valve can be easily broken. It can be done 

by removing the handle on the temperature controller, (noting carefully the assembly of the 

components), rotating the internal stops a few degrees in the required direction and then 

reassembling. All the commissioning checks should be redone again to ensure it now meets 

the required specification before using the shower.

Содержание Atmos Zinc

Страница 1: ...Thermostatic Concentric Mixer Valve with Fixed Head Wall Arm Atmos Zinc Thermostatic Concentric Mixer Valve with Fixed Head Wall or Ceiling Arm Customer Care 0845 505 2211 TMV2 Approval property of T...

Страница 2: ...8 liters per minute the appliance must be capable of raising the water temperature to a minimum of 52 C The water temperature at the inlet to the mixer valve must remain relatively constant when flow...

Страница 3: ...a point not less than 25mm above the spill over level of the relevant bath shower tray or other fixed appliance A double check valve or similar MUST be fitted in the supply pipework to prevent back fl...

Страница 4: ...hot and cold water pressures If this is not the case a flow controller disc with small holes can be fitted to the higher pressure supply to the valve This is best done by testing each one to find out...

Страница 5: ...th Wall Arm Atmos Zone Concealed Valve with Wall Arm Atmos Zinc Concealed Valve with Ceiling Arm Atmos Zinc Consult the illustration below to make sure you check from the component list that all the p...

Страница 6: ...water pressures to hot and cold are the same these disks do not need to be used CONCENTRIC VALVE SET UP 1 Your thermostatic concentric mixer valve is set up in the factory so that a shower hose can be...

Страница 7: ...getting into the openings while fitting the pipework You should measure the distance between the outlets on the mixer valve you are fitting to determine the exact distance 3 Complete the fitting of t...

Страница 8: ...nnecting the water supplies and checking the connections when running the shower and when the shower is off TRIM PLATE FITTING FOR Atmos Zinc Zone 1 The trim plate is fitted by pushing it onto the mix...

Страница 9: ...arm drill a suitable 19mm hole through the wall NOTE When fitting to stud wall a bearer between the uprights maybe required 3 Remove fittings and nuts from end of arm and push arm through wall re fit...

Страница 10: ...fit a cross bearer between two joists Drill suitable 19mm hole through ceiling See Fig 23 3 Remove fittings and nuts from end of arm and push arm through wall re fit washer and nut 4 Connect mixed wat...

Страница 11: ...ew Then turning the splined shaft clockwise to decrease the temperature colder or anti clockwise to increase the temperature hotter when you have achieved a temperature of 38 C re assemble the tempera...

Страница 12: ...the heating system F Hot water supply blocked or restricted G Pressure in excess of max recommended SUGGESTED ACTION Adjust the temperature control this is only a job for a suitably qualified person T...

Страница 13: ...Showerhead Reduce simultaneous demand Check stop service valves are fully open Check if enough water pressure Fit reducing disc to outlet of valve Renew flow control cartridge see parts list COMPONEN...

Страница 14: ...IT SPARE PARTS Atmos Zinc 1 Fixed Overhead ZLK 2 Wall Arm ZLJ 3 Ceiling Arm ZLI 4 Valve only 36HLW ZLD VALVE SPARE PARTS LIST 5 Fitting Kit 36HLW ZJK 6 Cartridge All in one ZJA 7 Square Cover Plate ZJ...

Страница 15: ...14 ACCESSORIES KIT SPARE PARTS Atmos Zone 1 Fixed Overhead ZLS 2 Valve only 36HLW ZLG VALVE SPARE PARTS LIST 3 Fitting Kit 36HLW ZJK 4 Cartridge all in one ZJA 5 Cover Cover Plate ZJV 1 2 3 4 5...

Страница 16: ...hout charge provided the product has been properly installed maintained and operated in accordance with the operating instructions This product must not be modified repaired or taken apart except by a...

Страница 17: ...5 This guarantee applies to an original installation in accordance to our fitting instructions and does not cover previously installed products showroom displays etc or products that have been moved f...

Страница 18: ...our part for death or personal injury resulting from our negligence 4 Except as stated above and to the fullest extent permitted by law all conditions warranties and representations whether express o...

Страница 19: ...e on parts or products not supplied as part of the product 4 A charge will be made in the event of a service call aborted by you but not by us or where a call under the terms of guarantee has been boo...

Страница 20: ...Cross Limited Trading as The MX Group Alpha Close Delta Drive Tewkesbury Industrial Estate Tewkesbury Glos GL20 8JF www mx group com email mixervalves mx group com Customer Care 0845 505 2211 6752A 0...

Отзывы: