Technical Data
User manual 9000-41011-0200000_hdb_en_20
58 / 92
NOTE
A high-energy impulse (surge) applied to the output of the Mico Pro modules
can cause short-term voltage interruption (max. 3 ms). This protects the con-
nected loads. Mico Pro detects within this time, whether a faulty short circuit
or a high-energy impulse occurred. If there is no short circuit, Mico Pro will be
switched on again.
Output variants: Number of channels, Tripping current (I
N
), Output current (I
∑
),
Tripping current setting range, Power-up delay
Art.-No.
Parameter
Conditions
Value
9000-41091-0101000 Number of channels
1
Tripping current (I
N
) Full load
10 A (+20%)
Tripping current set-
ting range
Selectable for
each channel
1 A, 2 A, 3 A, 4 A, 5 A,
6 A, 7 A, 8 A, 9 A, 10 A
9000-41091-1102000 Number of channels
1
Tripping current (I
N
) Full load
20 A (-5% ... +15%)
Tripping current set-
ting range
Selectable for
each channel
11 A, 12 A, 13 A,
14 A, 15 A, 16 A,
17 A, 18 A, 19 A, 20 A
9000-41092-0101000 Number of channels
2
Tripping current (I
N
) Full load per
channel
10 A (+20%)
Output current (I
∑
)
Full load all
channels
20 A
Tripping current set-
ting range
Selectable for
each channel
1 A, 2 A, 3 A, 4 A, 5 A,
6 A, 7 A, 8 A, 9 A, 10 A
Power-up delay
Per channel to
avoid inrush
current peaks
75 ms
9000-41094-0101000 Number of channels
4
Tripping current (I
N
) Full load per
channel
10 A (+20%)
Output current (I
∑
)
Full load all
channels
40 A
Tripping current set-
ting range
Selectable for
each channel
1 A, 2 A, 3 A, 4 A, 5 A,
6 A, 7 A, 8 A, 9 A, 10 A
Power-up delay
Per channel to
avoid inrush
current peaks
75 ms
Содержание Mico Pro fix 1.10
Страница 1: ...MANUAL Mico Pro Murrelektronik GmbH ...