Technical Data
User manual 9000-41011-0200000_hdb_en_20
25 / 92
4.1.2
Environmental characteristics
4.1.2.1
Climatic
4.1.2.2
Mechanical
Variants Output: Input failure bridging, Start-up time, Short-circuit current, Out-
put capacitance, Return current when switched-off
Art.-No.
Parameter
Conditions
Value
9000-41190-0000105
Input failure bridging
115 V
>20 ms
Input failure bridging
230 V
>65 ms
Start-up time
115 V
<300 ms
Start-up time
230 V
<300 ms
Short-circuit current
7 A
Output capacitance
4070 µF
Return current when
switched-off
27 mA
9000-41190-0000110
Input failure bridging
115 V
>44 ms
Input failure bridging
230 V
>44 ms
Start-up time
115 V
<175 ms
Start-up time
230 V
<200 ms
Short-circuit current
15 A
Output capacitance
5270 µF
Return current when
switched-off
30 mA
Parameter
Conditions
Value
Output rise time
17 ms
Short-circuit energy
i
2
t
Infinite A
2
s
Extra current / hyper boost
No
Max. switchable capacity on the
output
Infinite
Touch Current
<0.1 mA
Parameter
Conditions
Value
Operating temperature
-25 ... +55 °C
Operating temperature
Art.-Nr. 9000-41190-0000110
@90 ... 160 V
-25 ... +50 °C
Relative humidity
no condensation
5 ... 95 %
Storage temperature
short-term
-40 ... +85 °C
Storage temperature
long-term
+5 ... +35 °C
Climate class
EN 60721
3K3
Climate class
EN 60721
3C1
Installation height
-500 m ... 2000 m
Art.-No.
Parameter
Conditions
Value
9000-41190-0000105
Vibration test
3 axis, 60 minutes
2-17.8Hz:
±1.6 mm
17.8-500 Hz:
2,0g
Shock test
1 shock/s, 3 axis,
3 pos. & 3 neg. per
axis
15 g / 11ms
Содержание Mico Pro fix 1.10
Страница 1: ...MANUAL Mico Pro Murrelektronik GmbH ...