Technical Data
User manual 9000-41011-0200000_hdb_en_20
50 / 92
4.6
Mico Pro fix CL2 module
4.6.1
Electrical data
4.6.1.1
Input
4.6.1.2
Output
Parameter
Conditions
Value
Operating voltage
12 V
, 24 V
Input voltage range
9 V - 30 V
Total operating current continuous
jumper
Plug-In link
40 A
Parameter
Conditions
Value
Circuit element
Static switch
Module initialization time
250 ms
Parallel connection
Not possible
Series connection
Cascading in 2 steps
(see chapter 7 "Operation")
Disconnecting characteristics accu-
racy
Current
0 % … +9 %
Nominal output voltage
Same as input
Turn-on capacity
Until SW 1.01;
1 channel, depen-
dent on: component
tolerance, wire
length, used power
supply, load current,
selected current
range
≤20 mF
Turn-on capacity
1 channel, depen-
dent on: component
tolerance, wire
length, used power
supply, load current,
selected current
range
≤30 mF
Variants Output: Number of channels, Tripping current (I
N
), Output current (I
∑
),
Power-up delay
Art.-No.
Parameter
Conditions
Value
9000-41011-0400001
Number of channels
1
Tripping current (I
N
)
Full load
3 ... 4 A
(+9%)
9000-41014-0400001
Number of channels
4
Tripping current (I
N
)
Full load per channel 3 ... 4 A
(+9%)
Output current (I
∑
)
Full load all channels 16 A
Power-up delay
Per channel to avoid
inrush current peaks
75 ms
Содержание Mico Pro fix 1.10
Страница 1: ...MANUAL Mico Pro Murrelektronik GmbH ...