Section 80
00-02-0829
2018-02-26
-
36 -
4.4.1.1 Output Command Identifier
This value defines which output channels the Command Output Channels message is referencing.
4 Output Channels 1-6
5 Output Channels 7-12
Data Length:
1 byte
Resolution:
2 states / 1 byte
0 offset
Data Range:
4 or 5
Operational Range: same as data range
Type:
Status (command)
PGN:
4.4.1.2 Command
This value defines the output channel’s PWM value as a percentage.
This is a signed value (msb is the sign bit).
Note:
When an output is either disabled or the second channel in an
H-bridge pair, the command should be set to 0 for that channel.
0 0%
1 +0.78125%
…
127 +100%
128 -100%
…
255 -0.78125%
Data Length:
1 byte
Resolution:
0.78125 % / lsb
0 offset
Data Range:
-100% to +100%
Operational Range: same as data range
Type:
Status (command)
PGN:
IMPORTANT: It may be necessary to turn on the outputs in a
staggered manner when multiple high-currents loads need to be
energized due to the high inrush current.
Содержание Xpansion IX3212
Страница 1: ...00 02 0829 2018 02 26 Section 80 Intelligent Xpansion Series IX3212 PDM Reference Manual ...
Страница 10: ...Section 80 00 02 0829 2018 02 26 8 2 2 Dimensions IX3212 PDM Dimensions ...
Страница 61: ...NOTES ...
Страница 62: ......