Air Conditioner DC Duct Type
EN
13
Código interruptor de palanca
4
5
8
9
9
Capacidad (Btu/h)
18000
24000
36000
48000
60000
CAUTION
1.The system together have 64units
(0-63),everyone has only system addresscode,
If two addresses are the same in one system,
the abnormal operation will occur.
2.Please switch off the power before
setting,otherwise the unexpected error will occur.
Network address
code
00-15
16-31
32-47
48-63
13. NETWORK ADDRESS SET
Every air-conditioner in network has only one
network address to distinguish each other.
Address code of air-conditioner in LAN is set by
code switch on Network Interface Module (NIM),
and the set range is 0-63
N°
Type
Contents
LED Lamp Flash
Remarks
1
Malfunction
2
Malfunction
3
Malfunction
4
Malfunction
5
Alarm
The evaportator sensor check point
is abnormal, or room temp. sensor
is abnormal
Indoor/Outdoor unit comunication
is abnormal
Condenser sensor check point is
abnormal or outdoor temp. sensor
is abnormal
Water level switch is abnormal
Mode conflict
Run lamp flashes at 2.5 Hz
The timer lamp flashes
at 2.5 Hz
All the indoor alarm lamps
flash at 0,5 Hz
Alarm lamp flashes
at 2.5 Hz
Defrost lamp flashes
at 2.5 Hz
After the malfunctions disappear,
it restores automatically
After the malfunctions disappear,
it restores automatically
After the malfunctions disappear,
it restores automatically
If the malfunctions can't be solved
in three min. all the indoor alarm
lamp flashes at 0,5Hz.
Turn off the power to restore.
When the indoor unit turns to
heating mode or is turned off, the
alarm will disappear
Содержание MUCR 12 HF
Страница 11: ...ES 10 Aire Acondicionado DC Conducto 12 ESQUEMAS ELECTRICOS 18000 24000 Btu h 36000 60000 Btu h...
Страница 12: ...ES 11 Aire Acondicionado DC Conducto 12 ESQUEMAS ELECTRICOS 18000 24000 Btu h 36000 60000 Btu h...
Страница 28: ...10 12 WIRING CHART Air Conditioner DC DuctType EN...
Страница 29: ...Air Conditioner DC DuctType EN 11 12 WIRING CHART...