Air Conditioner DC Duct Type

EN

14

14. TEST OPERATION

1.The test operation must be carried out after the
entire installation has been completed.

2. Please confirm the following points before the
test operation:

3. According to the user's requirement, install the
remote controller frame where the remote
controller's signal can reach the indoor unit
smoothly.

4. Test operation

Set the air conditioner under the mode of

The indoor unit and outdoor unit are installed

properly.

Tubing and wiring are correctly completed.
The refrigerant pipe systemis leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow

capacity of the refrigerant have been recorded.

The power voltage fits the rated voltage of the air

conditioner.

There is no obstacle at the outlet and inlet of the

outdoor and indoor and indoor units.

The gas-side and liquid-side stop values are both

opened.

The air conditioner is pre-heated by turning on

the power.

COOLING with the remote controller, and check
the following points per the Owner's Manual. If
there is any malfunction, please resolve it through
chapter "Troubles And Causes" in the Owner's
Manual.

1) The indoor unit
a. Whether the switch on the remote controller
works well.
b. Whether the buttons on the remote controller
works well.
c. Whether the air flow louver moves normally.
d. Whether the roomtemperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise
during operation.






2) The outdoor unit
a. Whether there is vibration or abnormal noise
during operation.
b. Whether the generated wind, noise, or
condensed water by the air conditioner have
influenced your neighborhood.
c. Whether any of the refrigerant is leaked.

A protection device delays the start of compressor
for about 3 minutes when it is restarted
immediately after switching on the power.

CAUTION

15. POINT CHECK INSTRUCTION

16. DISPLAY FUNCTION
INSTRUCTION

0.Normally display
1.Running mode:

0.Stand by
2.Cooling
3.Heating
4.Forced cooling

2.Runnig fan speed

0. Turn off
1. Low speed
2. High speed

3. Capacity demand
4. T3-Outdoor pipe temp.(Actual value)
5. TP-Discharge temp.(Actual value,if over

100degree,only display hundreds digit
and tens digit)

6.T4-Ambient temp.(Actual value)
7.Current of compressor
8.PMv opening degree
9.The last error or protection code
(Display 00 if no error)
10. Display

1. When stand by,LED displaying the amount of
indoor units online which
communicate with outdoor units
2. When operation,LED displaying frequecny value
of compressor
3. When defrost,LED displaying dF

Содержание MUCR 12 HF

Страница 1: ...MUCR 24 HF Manual de instalaci n MUCR 30 HF MUCR 36 HF MUCR 48 HF MUCR 60 HF ES Para realizar correctamente la instalaci n lea este manual antes de empezar El contenido de este manual puede estar suj...

Страница 2: ...CI N DEL PANEL 6 8 INSTALACI N DE LA TUBER A DE CONEXI N 7 9 CONEXI N DEL TUNBO REFRIGERANTE 8 10 CONEXI N DEL TUBO DE DESAG E 9 11 EL CTRICAS 9 12 ELECTRICOS 10 13 AJUSTE DE DIRECCIONES DE RED 13 14...

Страница 3: ...como recordarles que lean y conserven los manuales de instalaci n y de usuario 2 Aire Acondicionado DC Conducto 2 ACCESORIOS Manual de instalaci n 1 Mando a dist ncia 1 Aislante de los tubos 2 Tubo de...

Страница 4: ...s j En otras condiciones especiales IMPORTANTE a superf cie de apoyo debe ser plana y horizont l y capaz de soportar el peso de la unidad exteri r No debe haber otras fuentes de ruido o vibraci nes ay...

Страница 5: ...ente en el caso de un falso techo coloque los tubos de refrigerante desag e y los cables el ctricos de las unidades interior y exterior hasta los puntos de conexi n antes de colgar la m quina FORMA DE...

Страница 6: ...ese claramente cuando pregunte a sus clientes si necesitan una caja de entrada de aire y pregunte si la entrada es inferior o trasera ATENCI N Capacidad Btu h A B C D E F G H I J K M m n 18000 1082 10...

Страница 7: ...NOTA 5 Fije el cuerpo principal y el soporte exterior con el carril met lico de agujeros en dos posiciones Cuando cuelgue el soporte exterior con el ra l y con la correa presione fuerte el soporte ex...

Страница 8: ...llo antes de la conexi n expulse el aire del tubo refrigerante Debe expulsar el aire consulte vaciado del aire despu s de conectar la conducci n de refrigerante a las unidades interior y exterior Apri...

Страница 9: ...llave de baja de la v lvula de colector Ponga en marcha la bomba de vac o Cuando comience el bombeo afloje un poco la tuerca del terminal de mantenimiento de la v lvula de cierre B para comprobar si...

Страница 10: ...los detalles de instalaci n de los tubos C o E t 10 CONEXI N DEL TUBO DE DESAG E 1 Instalaci n del tubo de desag e de la unidad interior IMPORTANTE La salida tiene una rosca PTI utilice materiales par...

Страница 11: ...ES 10 Aire Acondicionado DC Conducto 12 ESQUEMAS ELECTRICOS 18000 24000 Btu h 36000 60000 Btu h...

Страница 12: ...ES 11 Aire Acondicionado DC Conducto 12 ESQUEMAS ELECTRICOS 18000 24000 Btu h 36000 60000 Btu h...

Страница 13: ...adro de terminales Consulte el esquema el ctrico de la unidad interior Los aires acondicionados se pueden conectar a un Monitor de Control Central CCM Antes de poner la unidad en marcha realice correc...

Страница 14: ...onamiento parpadea a 2 5Hz Una vez el error desparece las funciones se recuperan autom ticamente 2 Error Error de comunicaci n entre la unidad interior y exterior El temporizador parpadea a 2 5Hz Una...

Страница 15: ...uncionan bien c El deflector del aire de salida se mueve normalmente d Se ajusta bien la temperatura de la habitaci n e El indicador se enciende normalmente f Los botones del temporizador funcionan bi...

Страница 16: ...i la instalaci n es correcta y luego vuelva a conectar la alimentaci n al cabo de 3 minutos Si el problema todav a persiste contacte con su distribuidor local ELIMINACI N DEL ELECTRODOM STICO VIEJO En...

Страница 17: ...l 956 35 37 85 Fax 956 35 37 89 Av Enrique Gimeno 24 Pol C Transporte CP 12006 Tel 96 424 72 11 Fax 96 424 72 03 Juan Bautista Escudero 219 C Pol Las Quemadas CP 14014 Tel 957 32 27 30 Fax 957 32 26 2...

Страница 18: ...CR 30 HF MUCR 36 HF MUCR 48 HF MUCR 60 HF Air Conditioner DC Duct Type Installation Manual EN For correct installation read this manual before starting installation This manual may be subject to chang...

Страница 19: ...INSTALL THE MAIN BODY 5 7 PANEL INSTALLATION 6 8 INSTALL THE CONNECTING PIPE 7 9 REFRIGERANT PIPE CONNECTION 8 10 CONNECT THE DRAIN PIPE 9 11 WIRING 9 12 WIRING CHART 10 13 NETWORK ADDRESS SET 13 14 T...

Страница 20: ...uct improvement 2 ACCESORIES 3 CAUTIONS ON REMOTE CONTROLLER INSTALLATION Installation manual 1 Remote controller subassembly 1 Pipe insulation material 2 Accessory drain pipe 1 Adhesive tape for seal...

Страница 21: ...ot be reached by strong wind he place is dry and ventilative he support is flat and horizontal and can stand the weight of the outdoor unit And no additional noise or vibration our neighborhood will n...

Страница 22: ...ing to the ceiling varies fromthe constructions consult the construction personnels for the specific procedures Carry out the pipe and line operation in the ceiling after finishing the installation of...

Страница 23: ...erneath the dust proof net The static pressure in the outside of the unit is 39 2Pa maximum98Pa the length of the air pipe attached is determined by this parameter Pipe Connection THE POSITIONING OF C...

Страница 24: ...rame on the outside frame the inverse sequence of unloading the inner frame Connect the remote control receiver with the indoor unit signal wires and fix it 7 Install remote controller NOTE NOTE 7 PAN...

Страница 25: ...loosened for a long time dusts and other 2 Air Conditioner DC DuctType EN 7 NOTICE FOR BENDABLE PIPE BEND THE CONNETCTING PIPE OF SMALL WALL THICKNESS Use the market brass pipe The bending angle shoul...

Страница 26: ...ach air conditioner has two stop values of different sizes on the side of the outdoor unit which operate as Lo stop value and Hi stop value respectively Loosen and remove the maintenance nuts of stop...

Страница 27: ...Check all the joints with the leak detector or soap water Be sure to with insulating materials cover all the exposed parts of the flare pipe joints and refrigerant pipe on the liquid side and the gas...

Страница 28: ...10 12 WIRING CHART Air Conditioner DC DuctType EN...

Страница 29: ...Air Conditioner DC DuctType EN 11 12 WIRING CHART...

Страница 30: ...n connect with Central Control Monitor CCM Before operation please wiring correctly and set system address and network address of indoor units CAUTION The reserved function is indicated in broken line...

Страница 31: ...Flash Remarks 1 Malfunction 2 Malfunction 3 Malfunction 4 Malfunction 5 Alarm The evaportator sensor check point is abnormal or room temp sensor is abnormal Indoor Outdoor unit comunication is abnorma...

Страница 32: ...switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver moves normally d Whether the roomtemperature is adjusted well e Whet...

Страница 33: ...sure Protection P2 Low Pressure Protection P3 Compressor current protection P4 Compressor discharge temperature protection P5 Protecci n de alta temperatura P6 Module protection CAUTION Please cut off...

Страница 34: ...BARCELONA Head Office Proven a 392 pl 1 2 08025 BARCELONA Export Department export salvadorescoda com Tel 34 93 446 27 81 Fax 34 93 446 27 96 SALVADOR ESCODA S A EN Instalation Manual...

Отзывы: