8. INSTALL THE CONNECTING PIPE

CAUTION

CAUTION

CONNECT THE DRAIN PIPE

1)

CAUTION

Check whether the height drop between the indoor
unit and outdoor unit, the length of refrigerant pipe,
and the number of the bends meet the following
requirements:

Measure the necessary length of the connecting
pipe, and make it by the following way.

Connect the indoor unit at first, then the outdoor

unit.Bend the tubing in proper way. Do not harm to
them.

• Do not let air, dust, or other impurities fall in the
pipe systemduring the time of installation.
• The connecting pipe should not be installed until
the indoor and outdoor units have been fixed
already.
• Keep the connecting pipe dry, and do not let
moisture in during installation.

The outdoor unit is factory charged with
refrigerant. Some systems require additional
charging of regrigerant depending on pipe lengths.
The additional refrigerant to be charged can be
calculated fromthe following formule:

R = T X (L-5)m
R(g): Additional regrigerant to be carged
T(g): The length of the liquid pipe
L(m):The quantity of charged refrigerant per meter

Daub the surfaces of the flare pipe and the joint
nuts with frozen oil, and wrench it for 3~4 rounds
with hands before fasten the flare nuts.
(Refer to chart 16)
Be sure to use two wrenches simultaneously when
you connect or disconnect the pipes.

The stop value of the outdoor unit should be

closed absolutely (as original state). Every time
you connect it, first loosen the nuts at the part of
stop value , then connect the flare pipe
immediately (in 5 minutes). If the nuts have been
loosened for a long time, dusts and other

2)

Air Conditioner DC Duct Type

EN

7

NOTICE FOR BENDABLE PIPE

BEND THE CONNETCTING PIPE OF SMALL
WALL THICKNESS

Use the market brass pipe

The bending angle should not exceed 90 .

Bending position is preferably in the middle of the

bendable pipe. The larger the bending radius the

Do not bend the pipe more than three times.

Cut out a desired concave at the bending part of

the insulating pipe.

Then expose the pipe (cover it with tapes after

bending).

To prevent collapsing or deforming, please bend

the pipe at its biggest radius.

Use bender to get a small radius pipes.

better it is.

Be sure to use the same insulating materials when
you buy the brass pipe (more than 9mmthick).

1. Locate The Pipes
1)

2)

3)

4)
5)

6)

7)

Drill a hole in the wall (suitable just for the size

of the wall conduit, 90mmin general), then set on
the fittings such as the wall conduit and its cover.

Bind the connecting pipe and the cables

together tightly with binding tapes. Do not let air in,
which will cause water leakage by condensation.

Pass the bound connecting pipe through the

wall conduit fromoutside. Be careful of the pipe
allocation to do no damage to the tubing.

Connect the pipes.

Then, open the stemof stop valves of the

outdoor unit to make the refrigerant pipe
connecting the indoor unit with the outdoor unit
fluently flow.

Be sure of no leakage by checking it with leak

detector or soap water.

Cover the joint of the connecting pipe to the

indoor unit with the soundproof/insulating sheath
(fittings), and bind it well with the tapes to prevent
leakage.


Chart 16

Chart 17

Chart 18

18000

15
25

48000

20
40

60000

20
40

Capacity (Btu/h)
The max. height drop (m)
Lenght of refrigerant pipe
Number of bends (m)

24000

15
30

36000

20
40

Less than 15

Содержание MUCR 12 HF

Страница 1: ...MUCR 24 HF Manual de instalaci n MUCR 30 HF MUCR 36 HF MUCR 48 HF MUCR 60 HF ES Para realizar correctamente la instalaci n lea este manual antes de empezar El contenido de este manual puede estar suj...

Страница 2: ...CI N DEL PANEL 6 8 INSTALACI N DE LA TUBER A DE CONEXI N 7 9 CONEXI N DEL TUNBO REFRIGERANTE 8 10 CONEXI N DEL TUBO DE DESAG E 9 11 EL CTRICAS 9 12 ELECTRICOS 10 13 AJUSTE DE DIRECCIONES DE RED 13 14...

Страница 3: ...como recordarles que lean y conserven los manuales de instalaci n y de usuario 2 Aire Acondicionado DC Conducto 2 ACCESORIOS Manual de instalaci n 1 Mando a dist ncia 1 Aislante de los tubos 2 Tubo de...

Страница 4: ...s j En otras condiciones especiales IMPORTANTE a superf cie de apoyo debe ser plana y horizont l y capaz de soportar el peso de la unidad exteri r No debe haber otras fuentes de ruido o vibraci nes ay...

Страница 5: ...ente en el caso de un falso techo coloque los tubos de refrigerante desag e y los cables el ctricos de las unidades interior y exterior hasta los puntos de conexi n antes de colgar la m quina FORMA DE...

Страница 6: ...ese claramente cuando pregunte a sus clientes si necesitan una caja de entrada de aire y pregunte si la entrada es inferior o trasera ATENCI N Capacidad Btu h A B C D E F G H I J K M m n 18000 1082 10...

Страница 7: ...NOTA 5 Fije el cuerpo principal y el soporte exterior con el carril met lico de agujeros en dos posiciones Cuando cuelgue el soporte exterior con el ra l y con la correa presione fuerte el soporte ex...

Страница 8: ...llo antes de la conexi n expulse el aire del tubo refrigerante Debe expulsar el aire consulte vaciado del aire despu s de conectar la conducci n de refrigerante a las unidades interior y exterior Apri...

Страница 9: ...llave de baja de la v lvula de colector Ponga en marcha la bomba de vac o Cuando comience el bombeo afloje un poco la tuerca del terminal de mantenimiento de la v lvula de cierre B para comprobar si...

Страница 10: ...los detalles de instalaci n de los tubos C o E t 10 CONEXI N DEL TUBO DE DESAG E 1 Instalaci n del tubo de desag e de la unidad interior IMPORTANTE La salida tiene una rosca PTI utilice materiales par...

Страница 11: ...ES 10 Aire Acondicionado DC Conducto 12 ESQUEMAS ELECTRICOS 18000 24000 Btu h 36000 60000 Btu h...

Страница 12: ...ES 11 Aire Acondicionado DC Conducto 12 ESQUEMAS ELECTRICOS 18000 24000 Btu h 36000 60000 Btu h...

Страница 13: ...adro de terminales Consulte el esquema el ctrico de la unidad interior Los aires acondicionados se pueden conectar a un Monitor de Control Central CCM Antes de poner la unidad en marcha realice correc...

Страница 14: ...onamiento parpadea a 2 5Hz Una vez el error desparece las funciones se recuperan autom ticamente 2 Error Error de comunicaci n entre la unidad interior y exterior El temporizador parpadea a 2 5Hz Una...

Страница 15: ...uncionan bien c El deflector del aire de salida se mueve normalmente d Se ajusta bien la temperatura de la habitaci n e El indicador se enciende normalmente f Los botones del temporizador funcionan bi...

Страница 16: ...i la instalaci n es correcta y luego vuelva a conectar la alimentaci n al cabo de 3 minutos Si el problema todav a persiste contacte con su distribuidor local ELIMINACI N DEL ELECTRODOM STICO VIEJO En...

Страница 17: ...l 956 35 37 85 Fax 956 35 37 89 Av Enrique Gimeno 24 Pol C Transporte CP 12006 Tel 96 424 72 11 Fax 96 424 72 03 Juan Bautista Escudero 219 C Pol Las Quemadas CP 14014 Tel 957 32 27 30 Fax 957 32 26 2...

Страница 18: ...CR 30 HF MUCR 36 HF MUCR 48 HF MUCR 60 HF Air Conditioner DC Duct Type Installation Manual EN For correct installation read this manual before starting installation This manual may be subject to chang...

Страница 19: ...INSTALL THE MAIN BODY 5 7 PANEL INSTALLATION 6 8 INSTALL THE CONNECTING PIPE 7 9 REFRIGERANT PIPE CONNECTION 8 10 CONNECT THE DRAIN PIPE 9 11 WIRING 9 12 WIRING CHART 10 13 NETWORK ADDRESS SET 13 14 T...

Страница 20: ...uct improvement 2 ACCESORIES 3 CAUTIONS ON REMOTE CONTROLLER INSTALLATION Installation manual 1 Remote controller subassembly 1 Pipe insulation material 2 Accessory drain pipe 1 Adhesive tape for seal...

Страница 21: ...ot be reached by strong wind he place is dry and ventilative he support is flat and horizontal and can stand the weight of the outdoor unit And no additional noise or vibration our neighborhood will n...

Страница 22: ...ing to the ceiling varies fromthe constructions consult the construction personnels for the specific procedures Carry out the pipe and line operation in the ceiling after finishing the installation of...

Страница 23: ...erneath the dust proof net The static pressure in the outside of the unit is 39 2Pa maximum98Pa the length of the air pipe attached is determined by this parameter Pipe Connection THE POSITIONING OF C...

Страница 24: ...rame on the outside frame the inverse sequence of unloading the inner frame Connect the remote control receiver with the indoor unit signal wires and fix it 7 Install remote controller NOTE NOTE 7 PAN...

Страница 25: ...loosened for a long time dusts and other 2 Air Conditioner DC DuctType EN 7 NOTICE FOR BENDABLE PIPE BEND THE CONNETCTING PIPE OF SMALL WALL THICKNESS Use the market brass pipe The bending angle shoul...

Страница 26: ...ach air conditioner has two stop values of different sizes on the side of the outdoor unit which operate as Lo stop value and Hi stop value respectively Loosen and remove the maintenance nuts of stop...

Страница 27: ...Check all the joints with the leak detector or soap water Be sure to with insulating materials cover all the exposed parts of the flare pipe joints and refrigerant pipe on the liquid side and the gas...

Страница 28: ...10 12 WIRING CHART Air Conditioner DC DuctType EN...

Страница 29: ...Air Conditioner DC DuctType EN 11 12 WIRING CHART...

Страница 30: ...n connect with Central Control Monitor CCM Before operation please wiring correctly and set system address and network address of indoor units CAUTION The reserved function is indicated in broken line...

Страница 31: ...Flash Remarks 1 Malfunction 2 Malfunction 3 Malfunction 4 Malfunction 5 Alarm The evaportator sensor check point is abnormal or room temp sensor is abnormal Indoor Outdoor unit comunication is abnorma...

Страница 32: ...switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver moves normally d Whether the roomtemperature is adjusted well e Whet...

Страница 33: ...sure Protection P2 Low Pressure Protection P3 Compressor current protection P4 Compressor discharge temperature protection P5 Protecci n de alta temperatura P6 Module protection CAUTION Please cut off...

Страница 34: ...BARCELONA Head Office Proven a 392 pl 1 2 08025 BARCELONA Export Department export salvadorescoda com Tel 34 93 446 27 81 Fax 34 93 446 27 96 SALVADOR ESCODA S A EN Instalation Manual...

Отзывы: