7. WIRING CHART
1
Take out the faceplate,then dismantle the electronic control
cover plate.(see
Fig.7-1)
faceplate
cover plate
electronic control
electronic control
̚
Fig.7-1
the wire holder of power
cord(three-position))
the wire holder of signal
line (five-position))
cover plate
2 Individual connect the power cord and signal line.
(see
Fig.7-2)
Fig.7-3
Fig.7-2
An all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current
device(RCD)with the rating of above 10mA shall be
incorporated in the fixed wiring according to the nati-
onal rule.
CAUTION
Model(W)
7100~9000
16/10
8A
3x2.5
Manual switch
/
Insurance
(A)
Indoor unit power wiring (mm
2
)
Indoor/outdoor connecting wiring
(mm
2
) (3-core shielded wire)
Power
Phase
Fuse (A)
1-Phase
220-240V~ 50/60Hz
Frequency and volt
3x0.75
34(
34(
Signal wire for communicate
outdoor unit
Connect all shielding
layer of the shielding wires
Signal wire for communicate
indoor unit and outdoor unit
2SHQ
Control with groups
(All the shielding terminals of the shielding
wires connect to the metal plate of
the electric control box “ ”)
The last set unit needs to add matched resistance in the P, Q terminals
(The indoor unit accessory contains matched resistance).
3
4
Matched
Resistance
Installation manual
Wall mounted split D4+
7