mundoclima CL23215 Скачать руководство пользователя страница 9

WIRED CONTROLLER

To wired controller 

DISPLAY BOARD

The reserved wired control function is indicated in broken 
line table,users can purchase the wired controller when 
necessary

7.1   Terminal Board Diagram   

Please refer to the indoor unit wiring diagram for the wiring.

NOTE

The air-conditioners can be connected with Central Control 
Monitor (CCM). Before operation, please wiring correctly and 
set system address and network address of indoor units.

Single phase indoor unit

INDOOR UNIT POWER

220-240V

̚

̚

50/60Hz

    (Conventional)

XT1

Y/G

Y/G

RED

BLACK

/ 1

RED

BLACK

RED

BLUE

To central control 

Monitor (CCM) 

COMM. BUS 

To outdoor 

COMM. BUS

Please adopt the 3-core shielded wire.

7.2   Capacity setting

Horsepower code

Code

Capacity (HP)

0

1

2

3

4

2200W(0.8HP)

5600W(2.0HP)

4500W(1.5HP)

3600W(1.2HP)

2800W(1.0HP)

5

7100W(2.5HP)

Note: The horsepower
has been set before 
leaving the factory ,
anyone  can

̓

t

modify it except the 
maintenance person.

1

2

3

4

5

67

8

9A

B

C

D

E

F

0

ENC1

 

POWER_S

Setting

Toggle switch

ENC1

6

7

8000W(3.0HP)

9000W(3.2HP)

<(//2:

*5$<

P

Q

X

Y (E)

;7

:+,7(

%/8(

%/$&.

The system together have  64units(0-63), everyone has only 
system addresscode,If two addresses are the  same in one 
system, the abnormal operation will occur.

CAUTION

Installation manual

Wall mounted split D4+

8

Содержание CL23215

Страница 1: ... MVD Installation manual English CL23215 to CL23217 Wall Mounted Split www mundoclima com www mundoclima com ...

Страница 2: ... to let air substances go into refrigeration cycle Otherwise it will cause lower capacity abnormal high pressure in the refrigeration cycle explosion and injury Do not modify the length of the power supply cord or use of extension cord and do not share the single outlet with other electrical appliances Otherwise it will cause fire or electrical shock Carry out the specified installation work after...

Страница 3: ...sure proper drainage and insulate piping in order to prevent condensation Improper drain piping may result in water leakage and property damage Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough t...

Страница 4: ...apart from the nearest TV set or stereo equipment it is necessary to prevent image disturbances or noise interferences Do not install the remote controller in a place exposed to direct sunlight or close to a heating source such as a stove Note that the positive and negative poles are right positions when loading batteries This manual is subject to changes due to technological improvement without f...

Страница 5: ...of the room is perfect The indoor unit should be installed 2 5 meters or more above the floor Installation in the following places may cause trouble If it is unavoidable please consult with the local dealer A place full of machine oil A saline place such as coast A place full of sulfide gas such as hot spring resort Places where there are high frequency machines such as wireless equipment welding ...

Страница 6: ...n the outdoor unit and bend and arrange the pipe carefully Do not allow the piping to let out from the back of the indoor unit Be careful not to let the drain hose slack Insulate both of the auxiliary piping Banding the drain hose under the auxiliary pipe Do not allow the piping to let out from the back of the indoor unit 43 Indoor unit outline Connective pipe Fix the end of the connective pipe Re...

Страница 7: ...Double span should be used when connecting pipesof Indoor Unit Table 6 1 NOTE Please refer to installation instructions for the refrigerant piping conection of the air conditioner that with throttle device inside Tightening Torque Φ6 4 Outer diameter mm of connection piping Φ9 5 Tightening Torque N m 32 7 39 9 Φ15 9 61 8 75 4 Φ19 1 97 2 118 6 14 2 17 2 Table 6 2 Φ12 7 49 5 60 3 Fig 5 9 Fig 5 10 Co...

Страница 8: ...iring according to the nati onal rule CAUTION Model W 7100 9000 16 10 8A 3x2 5 Manual switch Insurance A Indoor unit power wiring mm2 Indoor outdoor connecting wiring mm2 3 core shielded wire Power Phase Fuse A 1 Phase 220 240V 50 60Hz Frequency and volt 3x0 75 3 4 3 4 Signal wire for communicate outdoor unit Connect all shielding layer of the shielding wires Signal wire for communicate indoor uni...

Страница 9: ...XT1 Y G Y G RED BLACK 1 RED BLACK RED BLUE To central control Monitor CCM COMM BUS To outdoor COMM BUS Please adopt the 3 core shielded wire 7 2 Capacity setting Horsepower code Code Capacity HP 0 1 2 3 4 2200W 0 8HP 5600W 2 0HP 4500W 1 5HP 3600W 1 2HP 2800W 1 0HP 5 7100W 2 5HP Note The horsepower has been set before leaving the factory anyone can t modify it except the maintenance person 1 2 3 4 ...

Страница 10: ...ping fan is 12 minutes Ș 11 means the time of stopping fan is 16 minutes 6 21 6 21 6 21 6 21 6 21 6 21 6 21 6 21 6 definition Ș 00 means temperature compensation is 6 degrees under heating mode Ș 10 means temperature compensation is 4 degrees under heating mode Ș 11 means temperature compensation is 8 degrees under heating mode Ș 01 means temperature compensation is 2 degrees under heating mode 6 ...

Страница 11: ...eted The refrigerant pipe system is leakage checked The drainage is unimpeded The heating insulation works well The ground wiring is connected correctly According to the user s requirement install the remote controller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remote controller and check t...

Страница 12: ... ASK FOR MORE INFORMATION Phone 34 93 446 27 80 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 MVD www mundoclima com ...

Отзывы: