26
Issue 13 (11/14/2017)
The battery charger will adjust the Equalize and Float voltages in proportion to the battery temperature by a factor
set in the Charger Temp Comp menu item. At temperatures above +25°C the compensation factor is subtracted
from the two voltages and at temperatures below +25°C the factor is added to the voltages
.
The calculated volt-
ages are limited in software to less than 44.0 VDC and greater than 33.0 VDC for a 36 VDC string and less than
58.0 VDC and greater than 44.0 VDC for a 48 VDC string.
If the temperature probe is disconnected or inop-
erative the Equalize and Float voltages will return to the default values fixed in hardware and no tempera-
ture compensation will take place.
Select the Charger Temperature Compensation voltage in volts per
degree C per cell. Arrow keys select from 2 mV to 6 mV in 0.1 mV steps.
Default: 3.9 mV/°C/cell.
accepts changes and exits,
discards
changes and exits.
The lowest battery voltage at which the battery charger will operate is adjustable from the Charger Threshold
menu. The charger will operate in a Trickle Charge mode until the battery voltage exceeds approximately 1.5
volts per cell.
Select the Charger Startup Threshold voltage. Arrow keys select from
15 to 27V for a 36V battery or 24 to 36V for a 48 V battery. Default:
27/36 V.
accepts changes and exits,
discards changes and exits
.
Input/Output Parameters
Select the line voltage at which the power supply transfers to Standby
mode. The value can range from 85 to 90 VAC with a
120V line or 170
to 180 VAC with a 240V line. Arrow keys
select the voltage. Default:
90/180 V.
accepts and exits,
discards changes and exits.
The actual Output Voltage is selected with a hardware jumper. Set the
selected voltage in this menu. Arrow keys select 63, 75, or 90 volts.
Default: 90 V.
accepts and exits,
discards changes and exits.
Current Alarm Parameters
Select the Current Alarm setting of AC output
n
, which can be
either
1 or 2. Arrow keys set the Current Alarm value between 1
and 22 A depending on the installed transformer. Default: 15 A.
Select the Global Current Alarm setting. This setting affects both outputs.
Arrow keys set the Current Alarm value between 1 and 22 A.
Default: 22 A.
accepts and exits,
discards changes and exits.
Содержание EB1s
Страница 2: ......
Страница 35: ...33 Issue 13 11 14 2017 Fig 8 1 Battery Balancer wiring 36V 3 batteries 1 string ...
Страница 36: ...34 Issue 13 11 14 2017 Fig 8 2 Battery Balancer wiring 48V 4 batteries 1 string ...
Страница 37: ...35 Issue 13 11 14 2017 Fig 8 3 Battery Balancer wiring 36V 6 batteries 2 strings ...
Страница 38: ...36 Issue 13 11 14 2017 Fig 8 4 Battery Balancer wiring 48V 8 batteries 2 strings ...