10
Issue 13 (11/14/2017)
2.5 Original
Shipping
Container
When returning a unit for service, use its original shipping container and all original packing materials. Items
damaged as a result of improper packaging will not be covered under provisions of warranty service.
2.6 Other Items
If you ordered other items such as batteries and cable kits for use with the power supply, ensure also that
those items did not sustain shipping damage. As with the power supply itself, all damage claims must be filed
with the shipping company and your Multilink representative should be contacted immediately.
Section 3:
Front
Panel Controls, Connections and Indicators
The front panel of each EB1s Series power supply contains various connectors, all operator controls and
indicators. These items are described as follows. Further details regarding use of controls and indicators may
be found in the
Startup and Operation
section of this manual.
3.1 Controls
BATTERY CIRCUIT BREAKER:
60-amp circuit breaker protects battery circuit and input wiring. This circuit
breaker is also used as a DC switch to apply and remove battery input to the power supply.
3.2 Connections
See figure
3-1
and
4-1
for connector locations.
OUTPUT CONNECTORS:
The power supply contains two power output connectors located on the upper left
portion of the front panel. The mating Anderson
®2
mini-powerpole connector provides the means for
connecting output power to the appropriate network power connector in the cabinet. The black connector is
hot, is identified as L (line); the white connector is ground return for the output, identified as N (neutral). Each
neutral contact is internally connected to frame ground of the power supply.
BATTERY INPUT:
Anderson
®2
Powerpole
®2
type 75 A connector: used for connecting the external battery to
the power supply.
BATTERY TEMPERATURE PROBE:
RJ-11 connector: provides connection the external temperature probe
for temperature compensated battery charging.
TAMPER SWITCH:
Mini Mate-N-Lok
®3
: connects the enclosure tamper switch to the status monitor circuits
within the power supply. This allows the status monitor circuit to report an open door on the enclosure. The
tamper switch can be normally open (active high) or normally closed (active low).
CABINET INDICATOR:
Mini Mate-N-Lok
®3
: connects the enclosure alarm and status lamps to the power
supply for external status indication. The power supply will activate an external green lamp to indicate normal
output voltage and will activate a red alarm lamp to indicate line failure.
SERIAL COMMUNICATION PORT:
RJ-45 connector: provides connection to external status monitoring
transponder. The signal provided is a serial data string in HMS-022 format.
2
ANDERSON and POWERPOLE are registered trademarks of Anderson Power Products, Sterling, MA
3
Mate-N-Lok is a registered trademark of TYCO Electronics, Harrisburg, PA
Содержание EB1s
Страница 2: ......
Страница 35: ...33 Issue 13 11 14 2017 Fig 8 1 Battery Balancer wiring 36V 3 batteries 1 string ...
Страница 36: ...34 Issue 13 11 14 2017 Fig 8 2 Battery Balancer wiring 48V 4 batteries 1 string ...
Страница 37: ...35 Issue 13 11 14 2017 Fig 8 3 Battery Balancer wiring 36V 6 batteries 2 strings ...
Страница 38: ...36 Issue 13 11 14 2017 Fig 8 4 Battery Balancer wiring 48V 8 batteries 2 strings ...