25
Issue 13 (11/14/2017)
Battery Selection Parameters
Select the number of Battery Strings. String voltage is set at the factory
and is not configurable. Either 1 or 2 strings are selectable.
accepts changes and exits,
discards changes and exits
.
Arrow keys select the interval to test for Missing Batteries from 5 to 30
minutes. Select OFF to disable this feature. Default: OFF.
accepts changes and exits,
discards changes and exits
.
Low Battery Shutdown Parameters
Select the Low Battery Shutdown voltage in volts per cell.
The selected
value is represented as volts per cell and as the total battery string value.
The latter value will change depending on whether a 36 or 48 volt battery
string is configured. Arrow keys select from 1.65 volts to 1.80 volts. A indicates the default value. A down
arrow (
) indicates the lowest allowable setting. An up arrow (
) indicates the highest allowable setting.
Default: OFF.
accepts changes and exits,
discards changes and exits
.
Enable or disable Low Battery Monitoring. This feature works only
with the installation of a Battery Balancer module. Low Battery
Monitoring will shut down the inverter and put the power supply in a safe
“Sleep” mode if any single battery voltage drops below the setting in the “Shutdown Voltage” Configuration Menu
page. Default: OFF.
accepts changes and exits,
discards changes and exits
.
Battery Charger Parameters
The voltage levels for the battery charger Equalize and Float modes of operation are configurable within a speci-
fied range. These two settings are interactive - the Equalize voltage cannot be decreased to a value less than 50
millivolts above the Float voltage and the Float voltage cannot be increased to a value greater than 50 millivolts
below the Equalize voltage.
The leftmost character on the third line of the display indicates the status of the indicated value. A indicates the
default value. A down arrow (
) indicates the lowest allowable setting. An up arrow (
) indicates the highest
allowable setting. If attempting to select a value that would violate the 50 millivolt separation between Equalize
and Float mod
e settings, a letter symbol appears indicating that such a threshold has been reached, an ‘ ’ in the
case of the Equalize setting, or an ‘ ’ in the case of the Float setting.
The selected value is represented as volts per cell and as the total battery string value. The latter value will
change depending on whether a 36 or 48 volt battery string is configured.
Select the Battery Equalize voltage in volts per cell. Arrow keys
select from 2.26 volts to 2.44 volts depending on the Float setting.
accepts changes and exits,
discards changes and exits.
Select the Battery Float voltage in volts per cell. Arrow keys select
from 2.10 volts to 2.35 volts depending on the Equalize setting.
accepts changes and exits,
discards changes and exits.
Содержание EB1s
Страница 2: ......
Страница 35: ...33 Issue 13 11 14 2017 Fig 8 1 Battery Balancer wiring 36V 3 batteries 1 string ...
Страница 36: ...34 Issue 13 11 14 2017 Fig 8 2 Battery Balancer wiring 48V 4 batteries 1 string ...
Страница 37: ...35 Issue 13 11 14 2017 Fig 8 3 Battery Balancer wiring 36V 6 batteries 2 strings ...
Страница 38: ...36 Issue 13 11 14 2017 Fig 8 4 Battery Balancer wiring 48V 8 batteries 2 strings ...