Quick Start Guide
Quick Start Guide
If not using Zone 2 it is required to seal off
the zone with a 3K3 EOLR�
Note: Steps 4 & 5 are required to meet
Class 4 of the Australian Standard�
5� Interconnect Multicom Relay Output
Input/COM:
To notify the alarm panel of MC4P
communication failure, ensure that one of the
MC4P relays is programmed to “COMM’s fail
event” (Relay 1 is programmed to this by default).
Connect the Multicom’s relay output to
one of the Alarm Panel’s Zone Inputs. It is
recommended that the zone on the alarm panel
be a 24 hour audible input.
See Option 38.
4� Interconnect Alarm Panel Relay Output
Relay/COM:
7RDOORZLPPHGLDWHQRWLÀFDWLRQ
of communication failure to the control room,
program one of the alarm panel’s relay outputs
to trigger immediately on PSTN/COMM fail.
Connect the alarm panel’s relay output to one
of the Multicom’s Zone Inputs then ensure that
the zone is enabled.
See Option 30.
3K3