Number of cylinders
16
Gas type: natural gas
X
Methane number, min.
L
60
Table 6: General conditions (for max. power)
Consumption
Number of cylinders
16
Lube oil consumption after 1000 h runtime
g/kWh
0.3
Table 7: Consumption
Model-related data (basic design)
Number of cylinders
16
Operating method: Four-stroke cycle, Otto engine, single-acting
X
Combustion method: Mixture charging, spark ignition
X
Number of cylinders
16
Cylinder arrangement: V-angle
Degrees (°)
90
Bore
mm
170
Stroke
mm
210
Displacement, cylinder
Liters
4.77
Displacement, total
Liters
76.27
Compression ratio
10.5
Standard housing connecting flange (engine main PTO)
SAE
00
Table 8: Model-related data (basic design)
Coolant system (HT circuit, referenced to max. power without HT heat extraction)
Number of cylinders
16
Coolant temperature (at engine connection: outlet to cooling equipment)
(w/o antifreeze)
A
°C
90
Coolant temperature (at engine connection: inlet from cooling equipment
(w/o antifreeze)
A
°C
78
Coolant temperature after engine, alarm
R
°C
95
Coolant temperature after engine, shutdown
L
°C
98
Coolant temperature to enable load application, min.
L
°C
40
Coolant antifreeze content, max.
L
%
50
Coolant pump: Volumetric flow
L
m³/h
80
Filling pressure in cooling system (cold)
R
bar
0.5
Pressure in cooling system, max.
L
bar
6.0
Pressure loss over engine with maximum flow rate
bar
3.1
Thermostat: Starts to open
R
°C
68
Thermostat: Opening stops (thermostat fully open and bypass closed
A
°C
78
Table 9: Coolant system (HT circuit, referenced to max. power without HT heat extraction)
26 | Product Summary | MS150121/00E 2015-07