355 – AL Open Load Cylinder B5
Cause
Corrective action
Disruption fault in injector wiring
to cylinder B5.
1. Check wiring of affected injector (→ Page 219).
2. Contact Service.
356 – AL Open Load Cylinder B6
Cause
Corrective action
Disruption fault in injector wiring
to cylinder B6.
1. Check wiring of affected injector (→ Page 219).
2. Contact Service.
357 – AL Open Load Cylinder B7
Cause
Corrective action
Disruption fault in injector wiring
to cylinder B7.
1. Check wiring of affected injector (→ Page 219).
2. Contact Service.
358 – AL Open Load Cylinder B8
Cause
Corrective action
Disruption fault in injector wiring
to cylinder B8.
1. Check wiring of affected injector (→ Page 219).
2. Contact Service.
359 – AL Open Load Cylinder B9
Cause
Corrective action
Disruption fault in injector wiring
to cylinder B9.
1. Check wiring of affected injector (→ Page 219).
2. Contact Service.
360 – AL Open Load Cylinder B10
Cause
Corrective action
Disruption fault in injector wiring
to cylinder B10.
1. Check wiring of affected injector (→ Page 219).
2. Contact Service.
365 – AL Stop MV-Wiring Ground
Cause
Corrective action
Short circuit of injector positive
connection to ground of one or
more injectors. Short circuit of
negative connection of one or
more injectors to ground.
1. Check cabling (→ Page 219).
2. Restart engine.
3. Contact Service.
448 – HI P-Charge Air
Cause
Corrective action
The charge-air pressure at sensor
B10 has violated upper limit value
1. The charge-air pressure is too
high.
1. Power reduction.
2. Check sensor B10 and replace as necessary.
3. Contact Service.
MS15060/01E 2018-12
| Troubleshooting | 99
TIM-ID: 0000068683 - 006