381 – AL Wiring TOP 1
ZKP-Number: 2.8006.638
Line disruption on digital input 1
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output, plant-side 1
(TOP 1).
u
Check wiring to plant.
382 – AL Wiring TOP 2
ZKP-Number: 2.8006.639
Line disruption on digital input 2
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output, plant-side 2
(TOP 2).
u
Check wiring to plant.
383 – AL Wiring TOP 3
ZKP-Number: 2.8006.640
Line disruption on digital input 3
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output, plant-side 3
(TOP 3).
u
Check wiring to plant.
384 – AL Wiring TOP 4
ZKP-Number: 2.8006.641
Line disruption on digital input 4
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output, plant-side 4
(TOP 4).
u
Check wiring to plant.