Temposonics
®
R-Series
V
EtherNet/IP™
Operation Manual
I 14 I
Start- and end positions of the position magnets
Consider the start and end positions of the position magnets during the installation. To ensure that the entire stroke length is electrically usable,
the position magnet must be mechanically mounted as follows.
RP5 with U-magnet
Reference edge of mounting
Sensor electronics housing
Start position
28 (1.1)
End position
66 / 71* (2.6 / 2.8*)
* Stroke length > 5000 mm (196.9 in.)
RP5 with magnet slider “S”, “N”, “V”, “G”
Sensor electronics housing
Reference edge of mounting
Start position
12 (0.47)
End position
82 / 87* (3.23 / 3.43*)
* Stroke length > 5000 mm (196.9 in.)
RP5 with block magnet
Reference edge of mounting
Sensor electronics housing
* Stroke length > 5000 mm (196.9 in.)
End position
68.5 / 73.5* (2.7 / 2.9*)
Start position
25.5 (1)
RH5 with ring magnet / U-magnet
Sensor electronics housing
Reference edge of mounting
Start position
51 (2.01)
End position
63.5 / 66* (2.5 / 2.6*)
* Stroke length > 5000 mm (196.9 in.)
RH5 with block magnet
Sensor electronics housing
Reference edge of mounting
Start position
48.5 (1.91)
End position
66 / 68.5* (2.6 / 2.7*)
* Stroke length > 5000 mm (196.9 in.)
Fig. 17: Start- & end positions of magnets, part 1
Controlling design dimensions are in millimeters and measurements in ( ) are in inches
Fig. 18: Start- & end positions of magnets, part 2
NOTICE
On all sensors, use only the active measurement stroke, which is
between the start and end positions. The magnet may move beyond
these positions.