Temposonics
®
R-Series
V
EtherNet/IP™
Operation Manual
I 29 I
7.3.4
In the ‘New Module’ window (Fig. 44) perform step 7.3.4.1 –
7.3.4.4 to configure the new generic ethernet module to the
R-Series EtherNet/IP™ sensor.
7.3.4.1
In the “Name” field enter the “Sensor Name” as described in
the “I/O Configuration tree” (it might be beneficial to include
reference to the device ID).
7.3.4.2
In the “Comm Format” field, to “Set the Comm Format” to
select Input Data - DINT - Run/Program from the drop down
menu
7.3.4.3
In the “Address / Host Name” field, select the IP address
option and enter the static IP address you assigned to the
sensor in chapter 6.1.
7.3.4.4
To set the “Connection Parameters” enter the following
connection parameters field information:
NOTICE
Enter the “
Connection Parameters
” and “
Comm Format
” exactly in
the following order in step 7.3.4.1 – 7.3.4.4, otherwise your sensor
may not function properly.
NOTICE
RPI limitations are:
•
2 ms up to 4800 mm stroke
•
4 ms up to 7620 mm stroke
Select the open module properties check box and click “OK”. The
“Module Properties” window opens.
7.3.4.1
7.3.4.2
7.3.4.3
7.3.4.4
7.4 Set Module RPI
7.4.1
Click the “Connection” tab. Set the “Requested Packet Interval”
(RPI) value and press “OK”. (The default value is 10 milliseconds,
but the sensor is capable of a RPI as low as 2 milliseconds).
Fig. 44: New Module window
Fig. 45:
New module properties
Fig. 46:
New generic module has been added to the network
7.5 Verify Generic EtherNet Module
7.5.1
Verify that the new sensor is listed on the I/O configuration tree.
Name
Instance field
Size field
Input assembly
101
50
Output assembly
100
–
Confguration assembly
10
20