HYDROCAL 1005 Manual for Installation and Operation
Page 32/111
4.3.8.
Flushing
Step
No.
Status of the components
[1]
Capacitive Sensor F0
“active”
[2]
Capacitive Sensor FI
“active”
[3]
Capacitive Sensor FII
“active”
[4]
Valve V6
“closed”
[5]
Flow meter
“not active”
[6]
Valve V1
“circulating”
[7]
Valve V3
“open”
[8]
Compressor K1
“active”
[9]
Valve V4
” open”
[10]
Valve V2
“closed”
[11]
Pump P1
“not active”
[12]
Valve V5
“open”
4.3.8.1. Safety function and error observation for flushing cycle
Observed Components
Detectable Errors
Filling Sensor 0, 1, 2
Operating in normal parameters
Measurement Chamber
Measurement Chamber offline
Pressure Sensor
No depression