background image

4 Modbus-Function 05 (Write Single Coil) 

Write Single Coil (writing of single states ON/OFF) is used to acknowledge the latching mode or the 
horns as well as to set clock outputs individually. 

4.1 Acknowledgement of latching mode 

For this purpose, the command 05 is sent to the address of the DGC-06 with the indication of the 
respective chapter 3.7 or 3.8 
The acknowledgment only takes place when the value ON(0xFF00) has been sent. 

4.2 Acknowledgement of horn 

For this purpose, command 05 is sent to the address of DGC-06 and register 0x7000. 
The acknowledgment only takes place when the value ON(0xFF00) has been sent. 

4.3 Activation of the single Watch Output via Modbus 

For this purpose, the command 05 is sent to the address of the DGC-06 with the indication of the 
respective chapter 3.12 with register 50 not being allowed. 

5 Modbus Function 06 (Write Single Registers) 

Write Single Registers (writing of single registers) is used to write on individual registers in the 
DGC-06. Currently, it is only possible to write on the own slave address. 
Modbus address 0 (see chapter 3.12). 

6 Modbus-Function 15 (Write Multiple Coils) 

Write Multiple Coils (writing multiple states OFF/ON) is used to set all watch outputs at once. The 
command must be sent to DGC-06 address with the indication of register 50 with a maximum length 
of 7 bits. 

7 Modbus Function 16 (Write Multiple Registers) 

Write Multiple Registers (writing of several registers) is used to write on several registers in the 
DGC-06. Currently, it is only possible to write on the own slave address. 
Modbus address 0 (see chapter 3.12). 
All other parameter changes are not permitted for safety reasons; therefore, the data direction is 
clearly defined from the warning system to the open Modbus side. Retroaction is not possible. 

List of Revisions 

Version 

Date 

Chapter 

Changes 

2022-04 

05.04.2022  All 

New Design 

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | GA_GC06_Modbus_supplement_E, 2022-04-05 | USA 221209 | Page 12 of 12

DGC6 Modbus Supplement – UserManual

Содержание Intec Controls PolyGard 2 DGC6

Страница 1: ...C 06 Modbus Modbus Supplement Version 2022 04 Release date 2022 04 05 Language English Name of file GA_GC06_Modbus_supple ment_E INTEC Controls 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 78...

Страница 2: ...This page intentionally left blank...

Страница 3: ...ng bits of digital sensors 8 3 8 Display of the alarms and the respective latching bits of analog sensors 8 3 9 Relay status of the signal relays signal relay addr 1 96 Modbus register addr 7001 7096...

Страница 4: ...ng into account the current safety procedures for control instal lations The required equipotential bonding connections also e g secondary potential to ground or ground ing measures are to be carried...

Страница 5: ...ement has been poisoned The above warranty is in lieu of all other express warranties obligations or liabilities A pre authorized RMA number issued by INTEC Controls is required for returns This warra...

Страница 6: ...s inactive The resistor circuitry is already integrated in a Modbus master controller 3 Modbus Function 03 Reading of Registers Read Holding Registers reading of holding registers is used to receive d...

Страница 7: ...verage value of analog sensors sensor addr 1 32 Modbus register addr 4001 4032 Figure 4 Average value of analog sensors sensor addr 1 32 Modbus register addr 4001 4032 3 5 Measuring range of digital s...

Страница 8: ...g sensors Here the representation in the hexadecimal form is easier to read because the data are transmitted in the following form 0xFFFF 0x F F F F 0b 1111 1111 1111 1111 Local latching DGC 06 latchi...

Страница 9: ...fault message relay is in register 8000 The following values are possible 1 Relay is not active 0 Relay is active not energized 1 Relay is active energized 3 11 Error codes Modbus register addresses 9...

Страница 10: ...se these are dis played in the registers of the measured values c Register address 9097d 9104d Local error of the 8 Gas Controller Modules 1x GC06 7x EP06 Here 0x8100 MP error Error with any locally c...

Страница 11: ...its of the extension module address_2 Relay 9 is bit 0 to relay 12 is bit 3 Address 4 Relay information bits of the extension module address 3 Relay 13 is bit 0 to relay 16 is bit 3 Address 5 Relay in...

Страница 12: ...al registers in the DGC 06 Currently it is only possible to write on the own slave address Modbus address 0 see chapter 3 12 6 Modbus Function 15 Write Multiple Coils Write Multiple Coils writing mult...

Отзывы: