3.12 DGC-06 Watch Outputs (WI), Modbus register addresses 50–57
In register 50, all watch outputs are shown as a byte as used for evaluation in
the DGC-06 system.
In the registers 51–57 the individual bit values are available as Integer values.
0 or 0x0000 = No output set
1 or 0x0001 = Switch on by clock
256 or 0x0100 = Switch on by Modbus
257 or 0x0101= Switch on by Modbus and clock
Figure 9: DGC-06
clock outputs (WI)
Digital inputs are not represented in registers (only possible by assigning to a relay output and using
its output information).
3.13 Data block: Output
Address 0: Own slave Modbus address at the X Bus
Address 1: Relay information bits of the first module (Controller Module)
Relay 1 is bit 0 to relay 4 is bit 3
Address 2: Relay information bits of the extension module address_1
Relay 5 is bit 0 to relay 8 is bit 3
Address 3: Relay information bits of the extension module address_2
Relay 9 is bit 0 to relay 12 is bit 3
Address 4: Relay information bits of the extension module address 3
Relay 13 is bit 0 to relay 16 is bit 3
Address 5: Relay information bits of the extension module address_4
Relay 17 is bit 0 to relay 20 is bit 3
Address 6: Relay information bits of the extension module address_5
Relay 21 is bit 0 to relay 24 is bit 3
Address 7: Relay information bits of the extension module address_6
Relay 25 is bit 0 to relay 28 is bit 3
Address 8: Relay information bits of the extension module address_7
Relay 29 is bit 0 to relay 32 is bit 3
The addresses 9 to 24 stand for hardware analog output 1 to analog out-
put 16.
The definition of the values is done between 0 and 10000 (full scale
value of the sensor).
Figure 10: DCG06_REL_AO
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | GA_GC06_Modbus_supplement_E, 2022-04-05 | USA 221209 | Page 11 of 12
DGC6 Modbus Supplement – UserManual