3.12 DGC-06 Watch Outputs (WI), Modbus register addresses 50–57 

In register 50, all watch outputs are shown as a byte as used for evaluation in 
the DGC-06 system. 
In the registers 51–57 the individual bit values are available as Integer values.  

0 or 0x0000 = No output set 
1 or 0x0001 = Switch on by clock 
256 or 0x0100 = Switch on by Modbus 
257 or 0x0101= Switch on by Modbus and clock 

Figure 9: DGC-06 
clock outputs (WI) 

Digital inputs are not represented in registers (only possible by assigning to a relay output and using 
its output information). 

3.13 Data block: Output 

Address 0:  Own slave Modbus address at the X Bus 
Address 1:  Relay information bits of the first module (Controller Module) 

Relay 1 is bit 0 to relay 4 is bit 3 

Address 2:  Relay information bits of the extension module address_1 

Relay 5 is bit 0 to relay 8 is bit 3 

Address 3:  Relay information bits of the extension module address_2 

Relay 9 is bit 0 to relay 12 is bit 3 

Address 4:  Relay information bits of the extension module address 3 

Relay 13 is bit 0 to relay 16 is bit 3 

Address 5:  Relay information bits of the extension module address_4 

Relay 17 is bit 0 to relay 20 is bit 3 

Address 6:  Relay information bits of the extension module address_5 

Relay 21 is bit 0 to relay 24 is bit 3 

Address 7:  Relay information bits of the extension module address_6 

Relay 25 is bit 0 to relay 28 is bit 3 

Address 8:  Relay information bits of the extension module address_7 

Relay 29 is bit 0 to relay 32 is bit 3 

The addresses 9 to 24 stand for hardware analog output 1 to analog out-
put 16. 
The definition of the values is done between 0 and 10000 (full scale 
value of the sensor). 

Figure 10: DCG06_REL_AO 

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | GA_GC06_Modbus_supplement_E, 2022-04-05 | USA 221209 | Page 11 of 12

DGC6 Modbus Supplement – UserManual

Содержание Intec Controls PolyGard 2 DGC6

Страница 1: ...C 06 Modbus Modbus Supplement Version 2022 04 Release date 2022 04 05 Language English Name of file GA_GC06_Modbus_supple ment_E INTEC Controls 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 78...

Страница 2: ...This page intentionally left blank...

Страница 3: ...ng bits of digital sensors 8 3 8 Display of the alarms and the respective latching bits of analog sensors 8 3 9 Relay status of the signal relays signal relay addr 1 96 Modbus register addr 7001 7096...

Страница 4: ...ng into account the current safety procedures for control instal lations The required equipotential bonding connections also e g secondary potential to ground or ground ing measures are to be carried...

Страница 5: ...ement has been poisoned The above warranty is in lieu of all other express warranties obligations or liabilities A pre authorized RMA number issued by INTEC Controls is required for returns This warra...

Страница 6: ...s inactive The resistor circuitry is already integrated in a Modbus master controller 3 Modbus Function 03 Reading of Registers Read Holding Registers reading of holding registers is used to receive d...

Страница 7: ...verage value of analog sensors sensor addr 1 32 Modbus register addr 4001 4032 Figure 4 Average value of analog sensors sensor addr 1 32 Modbus register addr 4001 4032 3 5 Measuring range of digital s...

Страница 8: ...g sensors Here the representation in the hexadecimal form is easier to read because the data are transmitted in the following form 0xFFFF 0x F F F F 0b 1111 1111 1111 1111 Local latching DGC 06 latchi...

Страница 9: ...fault message relay is in register 8000 The following values are possible 1 Relay is not active 0 Relay is active not energized 1 Relay is active energized 3 11 Error codes Modbus register addresses 9...

Страница 10: ...se these are dis played in the registers of the measured values c Register address 9097d 9104d Local error of the 8 Gas Controller Modules 1x GC06 7x EP06 Here 0x8100 MP error Error with any locally c...

Страница 11: ...its of the extension module address_2 Relay 9 is bit 0 to relay 12 is bit 3 Address 4 Relay information bits of the extension module address 3 Relay 13 is bit 0 to relay 16 is bit 3 Address 5 Relay in...

Страница 12: ...al registers in the DGC 06 Currently it is only possible to write on the own slave address Modbus address 0 see chapter 3 12 6 Modbus Function 15 Write Multiple Coils Write Multiple Coils writing mult...

Отзывы: