Model IR4000S
1
Quick-Start Guide
Special tools:
5mm Allen wrench for cover (included with unit)
0.1” flat-head screwdriver for wiring (included with unit)
Adjustable wrench for conduit or cable gland connections (not included).
Mounting:
Allow convenient access to the front panel display and magnet switch input.
Leave sufficient room to attach cabling. Keep cable run distances below specified limits.
Although the Model IR4000S is RFI-resistant, where possible, mount it away from heavy
power cabling, radio transmitters, or similar equipment.
Where possible, locate the IR4000S away from excessive heat and vibration and as free
as possible from wind, dust, water, and direct sunlight.
MODEL IR4000M
P/N 32580
CONFIG
MAN
S/N
0518
0539
CALIBRATION PROCEDURE
1. HAVE DETECTOR IN CLEAN AIR
2. APPLY MAGNET, AND WAIT FOR "AC"
ON DISPLAY
3. REMOVE MAGNET, WHEN d# IS
DISPLAYED, APPLY MAGNET TO
SELECT DETECTOR #
4. REMOVE MAGNET, FLASHING "AC"
IS DISPLAYED
5. WHEN "AC" IS STEADY, APPLY GAS
6. WHEN GAS IS DETECTED, "CP" IS
DISPLAYED
7. WHEN CALIBRATION IS COMPLETE,
"CC" IS DISPLAYED
8. REMOVE GAS
ALARM LED
WARN LED
YEAR OF CONSTRUCTION
Figure 1: IR4000S Outline and Mounting Dimensions, in inches [mm]
NOTE:
Nameplate is for reference purposes only and may not contain up-to-date
information.