![MSA General Monitors IR4000S Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/msa/general-monitors-ir4000s/general-monitors-ir4000s_instruction-manual_1846478037.webp)
Model IR4000S
33
9.2.5 Environmental
Specifications
Temperature Range
Operating -40°F to 167°F (-40°C to +75°C)
Storage -76°F to 185°F (-60°C to +85°C)
Humidity Range 5% to 100% RH non-condensing
9.2.6 Modbus
Interface
The Model IR4000S does not have built-in serial communications but can pass the
Modbus signals from the attached detector to the control room. It is not possible to
communicate with the IR4000S directly. For details on the Modbus registers, refer to the
IR400 Modbus programming manual available on our website
(www.MSAsafety.com/detection).