Model IR4000S
11
control room equipment (HOST). You must remove the cover from the IR4000S
enclosure to access these connectors. The inside of the cover includes a label that lists
the function of each connector location.
WARNING:
For safety, ground cabling must always be connected first, before other
cabling is connected. The 24 VDC power cabling should be connected last (and
disconnected first). Power supply connections to the IR4000S must remain OFF until all
wiring is completed and the start-up readiness checklist has been verified. Refer to the
manual for the power supply being used for instructions.
Figure 6: IR4000S Terminal Block Connectors
TB2 - Host Terminal
Pin #
SIGNAL
1 4-20mA
out
2
IR400 MOD -
3
IR400 MOD +
4 NOT
USED
5 NOT
USED
6 CAL/ARGC
7 RLY
RST
8 COM
9 +24V
IN
TB3 - Relay Terminal
Pin #
DE-ENERGIZED
ENERGIZED
1 ALARM-NC
ALARM-NO
2 ALARM-C ALARM-C
3 ALARM-NO
ALARM-NC
4 WARN-NC WARN-NO
5 WARN-C WARN-C
6 WARN-NO WARN-NC
7 FAULT-NC FAULT-NO
8 FAULT-C FAULT-C
9 FAULT-NO FAULT-NC
TB1 - Detector Terminal
Pin #
SIGNAL
1 4-20mA
IN
2 CAL
IN
3 COM
4 FRAME
GND
5
IR400 MOD +
6
IR400 MOD -
7 COM
8 +24V
9 +24V
TB1
Detector
TB2
HOST
TB3