7 Maintenance
Maschinenfabrik Reinhausen GmbH 2020
68
5788897/03 EN
VACUTAP
®
VVS
®
7. Remove screws with locking elements on the on-load tap-changer head
cover.
Figure 58: On-load tap-changer head cover
8. Lift off the on-load tap-changer head cover horizontally.
Figure 59: On-load tap-changer head cover
9. Extract insulating fluid via pipe connection S.
10. Open the stop-cock between oil conservator and on-load tap-changer.
ð
The insulating fluid flows out of the oil conservator into the oil com-
partment.
11. Extract insulating fluid via pipe connection S.