3 Product description
Maschinenfabrik Reinhausen GmbH 2020
22
5788897/03 EN
VACUTAP
®
VVS
®
Diverter switch operations at the rated switching capacity or permitted over-
load do not cause the pressure-operated relay to trip.
The pressure-operated relay responds to a pressure change and not to gas
accumulation under the pressure-operated relay. Gas accumulation under
the pressure-operated relay is normal.
3.1.4.2.2 Design/versions
There are two variants of the pressure monitoring device:
▪ DW 2000 for vertical installation
▪ DW 2000 for horizontal installation
The housing and the cover cap of the pressure monitoring device consist of
lightweight, corrosion-resistant metal.
Figure 9: Snap-action switch and pressure measuring element
1 Snap-action switch
2 Pressure measuring element
Содержание VACUTAP
Страница 1: ...On load tap changer VACUTAP VVS Operating Instructions 5788897 03 EN ...
Страница 82: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 82 5788897 03 EN VACUTAP VVS 9 Drawings ...
Страница 93: ......
Страница 94: ......
Страница 95: ......