background image

E5

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

attics* and crawl spaces. Follow the National Fuel Gas 

Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Com

-

bustion and Ventilation for required size of ventilation 

grills or ducts.

*IMPORTANT:

 Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled 

power vent, heated air entering the attic will activate 

the power vent.

IMPORTANT:

 Vent-free heaters add moisture to 

the air. Although this is beneficial, installing heater 

in rooms without enough ventilation air may cause 

mildew to form from too much moisture. See Fresh 

Air for Combustion and Ventilation, pages 3 

 

through 5. 

INSTALLATION

NOTICE:

 This heater is intended for the use as supple

-

mental heat. Use this heater along with your primary 

heating system. Do not install this heater as your pri

-

mary heat source. If you have a central heating system, 

you may run system’s circulating blower while using 

heater. This will help circulate the heat throughout the 

house. In the event of a power outage, you can use this 

heater as your primary heat source for the duration of 

the outage. 

heater, Gas furnace, Vented gas heater, Gas fire

-

place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.
Example:
Gas water heater  40,000 Btu/hr
Vent Free   20,000 Btu/hr
Total 

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the   

 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add venti

-

lation grills between the rooms. See Ventilation Air 

From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon

-

fined space. You will need no additional fresh air 

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: one 

within 12” of the ceiling and one within 12” of the floor 

on the wall connecting the two spaces (see options 1 

& 2 of figure 2). You can also remove door into adjoin

-

ing room (see option3, fig 2). Follow the National Fuel 

Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for 

Combustion and Ventilation for required size of ventila

-

tion grills or ducts.

 WARNING:

 Rework worksheet, adding the space 

of the adjoining unconfined space. The combined 

space must have enough fresh air to supply all ap

-

pliance in both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventila

-

tion grills or ducts. Connect these items directly to the 

outdoors or spaces open to the outdoors. These include 

Ventilation 

Gills into 

Adjoining 

Room - Op-

tion 1

Ventilation Gills into Ad-

joining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

INLET 

AIR

OUTLET 

AIR

VENTILATION CRAWL SPACE

TO CRAWL 

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 

ATTIC

OUTLET AIR

Figure 2

Figure 3.

Содержание MHVFBI10LPT

Страница 1: ...unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and Venti...

Страница 2: ...nd adults away from hot surfaces to avoid burns or clothing igni tion Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be carefully...

Страница 3: ...ill insure that enough air for proper combustion enters the heater 4 If heater shuts off do not relight until you provide fresh outside air If heater keeps shutting off it re quires servicing 5 Turn o...

Страница 4: ...n the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 or applicable local codes 3 Add the Btu hr of all the fuel burning appliances in the space such as Vent free heater Gas water SAFETY DEVICE...

Страница 5: ...d space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an ad...

Страница 6: ...Heater pilot and burner must be at least 18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surface...

Страница 7: ...mounting bracket is firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall ar eas between studs or solid walls concrete or masonry Note Wall...

Страница 8: ...Use of floor mounting feet will require you to use a 3 8 NPT street elbow to make gas connection CAUTION Never connect heater directly to the Propane supply This heater requires an external regulator...

Страница 9: ...for leaks in next section Low Pressure Test Pressure Equal To or Less Than psig 3 5 kPa 1 Close equipment shutoff valve see figure 13 2 Pressurize supply piping system by either using compressed air...

Страница 10: ...ition see figure 16 Note Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 4 Wait five 5 minutes Then smell for gas in cluding near the floor If you smell gas STOP...

Страница 11: ...brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit every 2 500 hours of operation or every three months We also recommend that you keep the burner tube and pilot...

Страница 12: ...thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner orifice...

Страница 13: ...g Gas Con nections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing a...

Страница 14: ...E14 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater...

Страница 15: ...E15 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater 70828...

Страница 16: ...purchase and description of problem in all communication LIMITED WARRANTY Mr Heater Inc warrants its heaters and accessories to be free from defects in material and workmanship for a period of 1 year...

Страница 17: ...procedimientos adecuados de instalaci n y operaci n Para obtener asistencia o informaci n adicional consulte con un instalador calificado agencia de servicios o compa a de gas LEA CUIDADOSAMENTE LAS I...

Страница 18: ...a quemaduras fuego explosiones descargas el ctricas e intoxicaci n con mon xido de carbono ADVERTENCIA Este artefacto est equipado para ser utilizado con gas natural o propano No se permite la convers...

Страница 19: ...ficaciones de ventilaci n 1 Construcci n muy peque a 2 Espacio abierto 3 Espacio cerrado Este calentador no se debe instalar en un espacio cerrado o en una construcci n muy peque a a menos que cumpla...

Страница 20: ...ue el Btu hr real usado es superior al m ximo de Btu hr que el espacio puede soportar Debe brindar aire fresco adicional Las opciones son las siguientes A Reelabore la hoja de trabajo y el espacio del...

Страница 21: ...gas LP V lvula de cierre del equipo Empalme de puesta a tierra Conexi n de prueba de presi n Separador de sedimentos Junta en T Llave para tuber a Una v lvula de cierre del equipo con certificaci n C...

Страница 22: ...a adhesiva para su env o Retire el soporte de montaje del panel trasero C mo retirar el panel delantero del calentador 1 Retire tres tornillos de la parte inferior delantera del panel delantero 2 Tire...

Страница 23: ...tando hacia abajo tal como se muestra en la Figura 12 Si la ventilaci n est hacia abajo lo protege de la lluvia helada o aguanieve CUIDADO Use s lo tuber as nuevas de acero o hierro negro Las tuber as...

Страница 24: ...r de trabajo de construcci n temporaria con un cilindro de propano recargable remoto S LO cuando el cilindro est en el exterior y el calentador se utilice con la manguera Mr Heater suministrada PELIGR...

Страница 25: ...de seguridad arriba descrita Si no siente olor a gas contin e con el paso siguiente 5 Gire la perilla de control de gas en sentido horario hacia la posici n PILOTO y mantenga la perilla presionada dur...

Страница 26: ...tase a C mo cerrar el gas hacia el artefacto p gina 1 1 para los modelos que no tienen termostato Rem tase a Resoluci n de problemas p ginas 14 y 15 PATR N DE LA LLAMA DEL QUEMADOR La Figura 23 muest...

Страница 27: ...inta minutos 2 Revise si el quemador y el piloto tienen tierra o polvo 3 Sople a trav s de los puertos las ranuras y los orificios del quemador Si la parte superior de la llama del piloto es de color...

Страница 28: ...n de encendido est presionado se produce chispa en el SDO piloto pero el mismo no se enciende 1 La perilla de control no est completamente presionada 2 La perilla de control no se mantuvo presionada d...

Страница 29: ...r Se forma un polvo blanco dentro de la caja del quemador o en los muebles o las paredes contiguas 1 Cuando se calientan los vapores de lustramuebles cera limpiadores de alfombra etc se transforman en...

Страница 30: ...QUE NO EST N BAJO GARANT A Cont ctese con el distribuidor autorizado del producto Si no pueden suministrarle repuestos originales llame al n mero 800 de Enerco Group Inc que aparece en la parte de at...

Страница 31: ...de presi n 1 14 70370 Panel de acero 1 15 70327 Soporte de montaje del panel de acero 2 16 70366 Termocupla 1 17 70826 Soporte de montaje del quemador BF 1 19 70396 Protecci n de calor Superior 1 20 7...

Страница 32: ...AS DE REPUESTO S LO EST N DISPONIBLES DIRECTAMENTE DE F BRICA Y DEBEN SER INSTALADAS POR UN SERVICIO T CNICO HABILITADO INFORMACI N PARA SOLICITAR PIEZAS DE REPUESTO COMPRAS los accesorios pueden comp...

Отзывы: