PAGE 42 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #5 (02/28/20)
MAINTENANCE
4. Plug a power tool into the GFCI receptacle such as an
electric drill (Figure 69). Squeeze the ON/OFF switch
on the drill and verify that the drill turns on.
Figure 69. GFCI Receptacle Test
5. Continue holding down the ON/OFF switch on the drill
and at the same time press the
TEST
button on the
GFCI receptacle.
6. Verify that the drill turns off when the
TEST
button is
pressed.
7. If the drill motor continues to run after the
TEST
button
is pressed then it can be determined that the GFCI
receptacle is not working properly and should be
replaced.
8. Press the
RESET
button to restore power to the GFCI
receptacle.
9. If the
RED
status LED (Figure 70) is
flashing
,
do not
use the GFCI receptacle and replace it immediately.
Figure 70. GFCI Receptacle (RED Flashing LED)
10. Repeat the above procedure for the other GFCI
receptacle (right-most), substituting CB5 circuit
breaker.
GREEN LED ON
GFCI
RECEPTACLE
ELECTRIC
DRILL
ON/OFF
SWITCH
TEST
BUTTON
RESET
BUTTON
GENERATOR STORAGE
For long-term storage of the generator the following is
recommended:
Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
Clean the entire generator, internal and external.
Cover the generator and store in a clean, dry place.
Disconnect the battery.
Make sure engine coolant is at the proper level.
If the generator is mounted on a trailer, jack the trailer
up and place it on blocks so the tires do not touch the
ground, or block and completely remove the tires.