DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #5 (02/28/20) — PAGE 31
GENERATOR START-UP PROCEDURE (MANUAL)
BEFORE STARTING
1. Place the
main, GFCI, and aux.
circuit breakers
(Figure 39) in the
OFF
position prior to starting the
engine.
Figure 39. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Make sure the
voltage selector switch
has been
configured for the desired output voltage.
3. Connect the load to the
receptacles
or the
output
terminal lugs
as shown in Figure 10. These load
connection points can be found on the output terminal
panel and the output terminal panel’s hard wire hookup
panel.
4. Tighten terminal nuts securely to prevent load wires
from slipping out.
5. Close all engine enclosure doors (Figure 40).
Figure 40. Engine Enclosure Doors
CAUTION
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation
when operating.
Direct exhaust away from nearby personnel.
WARNING
NEVER
manually start the engine with the
main, GFCI
or auxiliary
circuit breakers in the
ON
(closed) position.
MAIN
CIRCUIT
BREAKER
GFCI
CIRCUIT
BREAKER
AUXILIARY
CIRCUIT
BREAKER
INCORRECT
CORRECT
STARTING (MANUAL)
1. Place the
Auto-Off/Reset-Manual Switch
in the
MANUAL
position to start the engine (Figure 41).
Figure 41. Auto-Off/Reset-Manual Switch
(Manual Position)
2. Once the engine starts, let the engine run for 1–2
minutes (let the engine idle longer in cold weather
conditions). Listen for any abnormal noises. If any
abnormalities exist, shut down the engine and correct
the problem.
3. The generator’s frequency meter (Figure 42) should be
displaying the 60-cycle output frequency in
HERTZ.
Figure 42. Frequency Meter
AUTO
MANUAL
OFF/RESET
NOTICE
If the engine fails to start within a specified number of
attempts, the shutdown lamp will illuminate and the
Auto-Off/Reset-Manual Switch must be placed in the
Off/Reset position before the engine can be restarted.
NOTICE
The engine will pre-heat automatically in cold weather
conditions.“Glow Plug Hold” message will be displayed
and the engine will start automatically after pre-heating.
Содержание WHISPERWATT DCA45SSIU4F
Страница 2: ...PAGE 2 DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 PROPOSITION 65 WARNING ...
Страница 52: ...PAGE 52 DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 CONTROLLER WIRING DIAGRAM ...
Страница 53: ...DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 PAGE 53 NOTES ...