DCA45SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #5 (02/28/20) — PAGE 13
INSTALLATION
OUTDOOR INSTALLATION
Install the generator in an area that is free of debris,
bystanders, and overhead obstructions. Make sure the
generator is on secure, level ground so that it cannot slide
or shift around. Also install the generator in a manner so
that the exhaust will not be discharged in the direction of
nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected
from excessive moisture. Failure to do so will result in
deterioration of the insulation and will result in short circuits
and grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to
engine and alternator parts.
INDOOR INSTALLATION
Exhaust gases from diesel engines are extremely
poisonous. Whenever an engine is installed indoors the
exhaust fumes must be vented to the outside. The engine
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can
cause excessive back pressure which will cause the engine
to heat excessively and possibly burn the valves.
MOUNTING
The generator must be mounted on a solid foundation
(such as concrete) and set firmly on the foundation to
isolate vibration of the generator when it is running. The
generator must be mounted at least 6 inches above the floor
or grade level as referenced in the National Fire Protection
Association (NFPA 110, Chapter 7, section 7.4) handbook.
DO NOT
remove the metal skids on the bottom of the
generator. They are to resist damage to the bottom of the
generator and to maintain alignment.
CAUTION
Pay close attention to ventilation when operating the
generator inside tunnels and caves. The engine exhaust
contains noxious elements. Engine exhaust must be
routed to a ventilated area.
GENERATOR GROUNDING
If applicable, to guard against electrical shock and possible
damage to the equipment, it is important to provide a good
EARTH
ground (Figure 2).
Article 250 (Grounding) of the NEC handbook provides
guidelines for proper grounding and specifies that the cable
ground shall be connected to the grounding system of the
building as close to the point of cable entry as practical.
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper
b. Aluminum
2. When grounding of the generator (Figure 2) is required,
connect one end the ground cable to the ground lug
on the generator. Connect the other end of the ground
cable to the ground rod (earth ground).
3. NEC Article 250 specifies that the earth ground rod
should be buried a minimum of 8 feet into the ground.
NOTICE
The Occupational Safety and Health Administration
(OSHA) and the National Electrical Code (NEC)
recommend that if the generator is providing electrical
power to a structure (home, office shop, trailer or
similar), it
must
be connected to a grounding electrode
system, such as a driven ground rod (Figure 2).
NOTICE
ALWAYS
check with State, Province, District and
Municipalities for electrical grounding requirements
before using the generator.
NOTICE
Reference Conductor Grounding Table, Article 250
of the NEC handbook for proper conductor wire size.
Wire size is determined by the maximum amperage of
the generator.
NOTICE
When connecting the generator to any building’s
electrical system
ALWAYS
consult with a licensed
electrician.
Содержание WHISPERWATT DCA45SSIU4F
Страница 2: ...PAGE 2 DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 PROPOSITION 65 WARNING ...
Страница 52: ...PAGE 52 DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 CONTROLLER WIRING DIAGRAM ...
Страница 53: ...DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 PAGE 53 NOTES ...