PAGE 20 — DCA45SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #5 (02/28/20)
OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by various
methods, output terminal lugs, camlocks or the convenience
receptacles (Figure 10). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
110-amp,
main
circuit breaker is provided. Make sure to
switch
ALL
circuit breakers to the
OFF
position prior to
starting the engine.
Figure 10. Connecting Loads
U
V
W
LOAD
O
NEUTRAL
GROUND
HARD WIRE
HOOKUP PANEL
LOAD
GFCI
RECEPTACLE
LOAD
CS-6369
TWIST-LOCK
RECEPTACLES
CAMLOCKS
Overcurrent Relay
An
overcurrent relay
(Figure 11) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the overcurrent relay may trip. If the circuit
breaker can not be reset, the
reset button
on the
overcurrent relay must be pressed. The overcurrent relay
is located inside the control box.
Figure 11. Overcurrent Relay
TEST
MC
RESET
MC
NOTICE
Remember the
overcurrent relay
monitors the current
flowing from the
U,V, and W Output Terminal Lugs
to the load.
In the event of a short circuit or overcurrent condition,
it will automatically trip the 110-amp main breaker.
To restore power to the
Output Terminal Panel
, press
the reset button on the overcurrent relay and place the
main
circuit breaker in the
closed
position (
ON
).
Содержание WHISPERWATT DCA45SSIU4F
Страница 2: ...PAGE 2 DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 PROPOSITION 65 WARNING ...
Страница 52: ...PAGE 52 DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 CONTROLLER WIRING DIAGRAM ...
Страница 53: ...DCA45SSIU4F 60 HZ GENERATOR OPERATION MANUAL REV 5 02 28 20 PAGE 53 NOTES ...