PAGE 44 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
GENERATOR SHUT-DOWN PROCEDURES
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
1. Place both the
MAIN, GFCI and LOAD
circuit breakers
as shown in Figure 56 to the
OFF
position.
Figure 56. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the
Auto Off/Reset Manual Switch
(Figure 57)
in the
OFF/RESET
position.
Figure 57.
Auto Off/Reset Manual
itch
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel
are
OFF
(not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
WARNING
NEVER
stop the engine suddenly except in an
emergency.
AUTO
MANUAL
OFF/RESET
(CENTER)
EMERGENCY SHUTDOWN PROCEDURE
1. In the event of an emergency, push the
Emergency
Stop Pushbutton Switch
(Figure 58) to shutdown
the generator.
Figure 58.
Auto Off/Reset Manual
Sw
itch (OFF)