PAGE 18 — DCA300SSJU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (06/26/18)
SEQUENCING
These generators are capable of sequencing for control
of balanced maintenance schedules. As described
above, these generators can start and stop as demand
raises or lowers. In addition, if the units get to the point of
maintenance, it will ramp off and start the next generator to
relieve it based on the time remaining on the maintenance
timer.
After maintenance is performed, the maintenance timers
should be reset to the recommended service interval. This
is usually 250 hours depending on the engine oil type.
MAINTENANCE INTERVAL
Maintenance intervals are factory set for 250 hours.
The maintenance interval timer will count down to zero
indicating that it is time for the unit to be serviced.
Once the timer counts down to zero, a pre-alarm will appear
indicating that the unit is due for maintenance. To reset the
maintenance interval back to the default time of 250 hours,
press and hold the “Reset” button for ten seconds.
To reset the maintenance interval using the reset button,
the Maintenance Due pre-Alarm must be active, and the
Basler controller must display the “Overview Screen” (Main
Screen).
If the maintenance timer has not yet expired and it is
desired to reset the unit back to 250 hours, navigate back
to the settings menu. Settings Menu->System Parameters-
>Engine Statistics->Hours To Maintenance.
PASSWORD ENTRY 2.04 AND LOWER
When highlighted, press the “Edit” button. Username and
Password is required. User Name is
A
and Password is
A
. Use the up arrow button (
) and scroll to the alpha
character
A
, then press edit to select.
Next, the cursor will move to the
password
field, press the
up arrow button (
) and scroll to the alpha character
A
,
then press edit to select.
NOTICE
Ethernet communication is required when the
generators are configured for the sequencing mode
of operation.
GENERAL PARALLELING INFORMATION (OPTION)
The complete password sequence is shown in Figure 4.
The set-point for the desired hours until maintenance can
now be changed. Press edit to save.
Figure 4. Password Sequence 2.04 and Lower
PASSWORD ENTRY 2.04 AND HIGHER
User Name and Password is
A
.
Once prompted, the cursor will be in the user name field.
Press the down button (
) twice to highlight the
A
character.
Once the user name of
A
is populated in the user name
field, press the up arrow (
) button four times to highlight
the check box in the upper right corner of the screen. With
the check box highlighted press the edit button to accept
the entry.
The cursor will move to the password field. Again, press the
down arrow (
) button twice until the
A
is highlighted and
then press edit. Press the up arrow (
) button four times
to highlight the check box in the upper right corner of the
screen. With the check box highlighted press the edit button
to accept the entry. This completes the password entry.
The complete password sequence is as follows:
Figure 5. Password Sequence 2.04 and Higher
Pre-alarm Silence allows the user to suppress the toggling
of the alarm screen when a new Pre-alarm becomes active.
While a Pre-alarm is active, pressing the Alarm Silence
button will suppress the fault display.
This happens to be very handy function when the
“Maintenance Interval” Pre-Alarm occurs. Right after the
Pre-Alarm occurs it will begin toggling between the
pre-
alarm
and the
overview screen
.
While in this mode, pressing the reset button does not reset
the maintenance interval. In order to reset the maintenance
interval the overview screen
must
be selected.
Edit
Edit
Edit
Edit
Edit
Edit