PAGE 24 — DCA12SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (07/20/17)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the
voltage selector switch
(Figure 14). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the
voltage regulator
(VR)
control
knob
located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 14) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection..
Figure 14. Voltage Selector Switch
CAUTION
NEVER
change the position of the
voltage selector
switch
while the engine is running.
ALWAYS
place
circuit breaker in the
OFF
position before selecting
voltage
.
Table 7. Voltages Available
UVWO Output
Terminal Lugs
Voltage Selector Switch
3-Phase 240/139V Position
Voltage Selector Switch
3-Phase 480/270V Position
3Ø
Line-Line
208V
220V
240V
416V
440V
480V
1Ø
Line-Neutral
120V
127V
139V
240V
254V
277V
Voltage Selector Switch Single-Phase 240/120V Position
1Ø
Line-Neutral/
Line-Line
120V
Line-Neutral
N/A
N/A
240V
Line-Line
N/A
N/A
NOTICE
This generator can provide variable output voltages via
the voltage regulator control knob.
Maximum Amps
Table 8 shows the
maximum
amps the generator can
provide.
DO NOT
exceed the maximum amps as listed.
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Tables and show what amount of current is available at
the GFCI receptacles when the output terminals and twist
lock receptacles are in use. Be careful that your load does
not to exceed the available current capability at the
receptacles.
Table 8. Generator Maximum Amps
Rated Voltage
Maximum Amps
1Ø 120 Volt
277.8 X 2 amps (4 wire)
300 amps X 2 (Zigzag)
1Ø 240 Volt
138.9 amps (4 wire)
300 amps (Zigzag)
3Ø 240 Volt
300 amps
3Ø 480 Volt
150 amps
Table 9. 1Ø GFCI Receptacle Load Capacity
KW in Use
Twist Lock (C6369)
Available Load
Current (Amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
72.0
0
70.8
5 amps/receptacle
69.6
10 amps/receptacle
68.4
15 amps/receptacle
67.2
20 amps/receptacle
Table 10. 3Ø Generator Maximum Amps
KVA in Use
(UVWO Terminals)
Available Load
Current (Amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
125
0 amps/receptacle
121
5 amps/receptacle
117
10 amps/receptacle
113
15 amps/receptacle
108
20 amps/receptacle