MGate MB3660 Modbus Gateway
Web Console Configuration
4-27
Then open the exported CSV file to further configure.
Make sure to follow the format or an error will occur when the file is imported. The detail description of the
format is shown below.
Port Configuration Format
Item
Value
Note
mode_type
0, 1, 2, 3
0: RTU Slave
1: RTU Master
2: ASCII Slave
3: ASCII Master
basic_setting
(RTU/ASCII Slave
mode only)
PortIndex
1 to 8 (the MGate
MB3660-8 Series)
1 to 16 1 to 8 (the MGate
MB3660-16 Series)
Serial port number
SlaveID
(Slave ID )
1 to 255
basic_setting
(Master mode only)
PortIndex
1 to 8
Serial port number
InitDelay
(Initial delay)
0 to 30000 ms
MaxRetry
(Max. retry)
0 to 5
RespTout
(Response timeout )
10 to 120000 ms
InterFrameDelay
(Inter-frame delay )
10 to 500 ms,(0 for disable)
InterCharDelay
(Inter-character timeout)
10 to 500, (0 for disable)
cmd_setting
(Master mode)
PortIndex
1 to 8 (the MGate
MB3660-8 Series)
1 to 16 1 to 8 (the MGate
MB3660-16 Series)
Serial port number
cmdIndex
(Command index)
1 to 32
Max. up to 32 commands
per port
cmdEnable
(Enable)
0, 1
0: disable
1: enable
cmdName
(Name)
Name
Max. up to 40 characters