MGate MB3660 Modbus Gateway
Web Console Configuration
4-18
Parameters
Value
Description
Initial delay
0-30000 ms
Some Modbus slaves may take more time to boot up than
other devices. In some environments, this may cause the
entire system to suffer from repeated exceptions during
the initial boot-up. You can force the MGate to wait after
booting up before sending the first request with the Initial
Delay setting.
Max. retry
0-5
This is used to configure how many times the MGate will try
to communicate with the Modbus slave.
Response timeout
10-12000 ms
This is used to configure how long the MGate will wait for a
response from a Modbus slave.
To add a new command or modify the existing one, click the
Add
button or
Modify
button and a new dialog box
will appear. To remove Modbus commands, select the specific command and then click the
Remove
button.
To communicate with remote Modbus TCP slave devices, specify the Modbus command for each device. For
each Modbus read/write command, specify the internal memory address for data exchange. For the read
command, the information received from remote devices will be updated to the specified internal memory
address. For the write command, the data in the specified internal memory address will be sent to the remote
device. The data will be used to update the remote device register.
Each remote device may need more than one command for communication, so you will need to input all the
commands manually.