MGate MB3660 Modbus Gateway
Web Console Configuration
4-4
Parameter
Value
Notes
LAN mode
Dual Subnet, Single IP
Use two different IP addresses for the two Ethernet
ports, or use one IP address for both ports.
LAN IP configuration Static IP, DHCP, BootP, or
DHCP/BootP
Select
Static IP
if you are using a fixed IP address.
Select one of the other options if the IP address is set
dynamically.
LAN IP address
192.168.127.254 or
192.168.126.254
(or another 32-bit number)
The IP (Internet Protocol) address identifies the server
on the TCP/IP network.
LAN netmask
255.255.255.0
(or another 32-bit number)
Identifies the server as belonging to a Class A, B, or C
network.
LAN gateway
0.0.0.0
(or another 32-bit number)
The IP address of the router that provides network
access outside the server’s LAN.
Active LAN when
boot up
LAN1, LAN2
Select which LAN is active when booting up.
Ping remote host
0.0.0.0
(or another 32-bit number)
Remote server for ping test
DNS1
0.0.0.0
(or another 32-bit number)
This is the IP address of the primary domain name
server.
DNS2
0.0.0.0
(or another 32-bit number)
This is the IP address of the secondary domain name
server.
Serial Settings
The
Serial
tab is where each serial port’s communication parameters are configured. You can configure
Baudrate
,
Parity
,
Stop Bit
,
Flow Control
,
FIFO
,
Interface
,
RTS on delay
, and
RTS off delay
.
Parameter
Value
Baudrate
50 bps to 921600 bps
Parity
None, Odd, Even, Space, Mark
Stop Bits
1, 2
Flow Control
None, RTS/CTS, DTR/DSR, RTS Toggle
UART FIFO
Enable, Disable
Interface
RS-232
RS-422
RS-485, 2W
RS-485, 4W
RTS On Delay
0 to 100 ms
RTS Off Delay
0 to 100 ms
RTS Delay
The
RTS Toggle
function in flow control is used for
RS-232
mode only. This flow-control mechanism is
achieved by toggling the RTS pin in the transmission direction. When activated, data will be sent after the RTS
pin is toggled ON for the specified time interval. After data transmission is finished, the RTS pin will toggle OFF
for the specified time interval.